Laserfiche WebLink
• VM1 • <br />Vaporless Manufacturing,, Inc. <br />Quality Petroleum Equipment <br />Solutions for Over 20 Years <br />LDT- 890 Test Form & VMI Warranty Checklist <br />A <br />October I , 2006 <br />Test Information: <br />Date: 04/02/2009 Test Company: _EPIC Compliance Systems, LLC <br />Telephone: (209)462-7621 Contact: Nancy Le <br />Site I.D: California Stop Address: 2224 S. Manthey Rd. <br />City: Stockton State: CA Zip: 95206 <br />Type of Test Equipment: LDT-890 <br />Submersible Pump Identification: <br />MFG: Tokheim Model No: <br />Leak Detector Identification: <br />MFG: VMI Model No: 99LD-2000 Serial No: 07081291 <br />Replacement Leak Detector Identification: <br />MFG: Model No: <br />Line Conditions <br />=ILl <br />1. Type of Pipe: F.G. 2. Diameter of Pipe: 2" 3. Length of Pipe: 105ft. <br />4. Burial Depth of Leak Detector 44" 5. Kind of Fuel: 87 6. Date of Last Line Test: <br />Test Conditions <br />1. Operating Pump Pressure: 26 2. Gallon per hour test rate: 3 @ 10 psi <br />3. Static Line Pressure (Pump Off): 25 4. Bleedback Test (Pump Off): 75 mi. <br />5. Step -through time to full flow 2 seconds (0 psi. to full pump pressure, no leak) <br />6. Leak detector stays in Leak Search Position with a 3 GPH leak - Yes: X PASS No: <br />7. Was the leak detector adjusted — Yes: No: X <br />Symptoms <br />2. Stays in Slow Flow: <br />3. Other: <br />FAIL <br />************ If This Unit Is Returned Under Warranty Please Complete The Following *********** <br />Vaporless RGA#: <br />Telephone: <br />Customer Control #: <br />City: <br />Return By (Company): <br />Contact: <br />Address: <br />State: <br />(See Website - .www.vaporless.com. - Technical Bulletin 032805) <br />X3 <br />