Laserfiche WebLink
0 VM1 0 <br />Vaporless Manufacturing, Inc. <br />Quality Petroleum Equipment <br />Solutions for Over 20 Years <br />LDT- 890 Test Form & VMI Warranty Checklist <br />.t <br />October I , 2006 <br />Test Information: <br />Date: 04/02/2009 Test Company: _EPIC Compliance Systems, LLC <br />Telephone: (209) 462-7621 Contact: Nancy Le <br />Site I.D: California Stop Address: 2224 S. Manthey Road <br />City: Stockton State: CA Zip: 95206 <br />Type of Test Equipment: LDT-890 <br />MFG: Tokheim Model No: 585- Serial No: 585-16122 <br />Leak Detector Identification: <br />MFG: VMI Model No: 99LD-2000 Serial No: 06031392 <br />Replacement Leak Detector Identification: <br />MFG: Model No: Serial No: _ <br />Line Conditions <br />1. Type of Pipe: F.G. 2. Diameter of Pipe: 2" 3. Length of Pipe: 105Ft. <br />4. Burial Depth of Leak Detector: 42" 5. Kind of Fuel: Diesel 6. Date of Last Line Test: --- <br />Test Conditions <br />1. Operating Pump Pressure: 29 2. Gallon per hour test rate: 3 @ 10 psi <br />3. Static Line Pressure (Pump Off): 29 4. Bleedback Test (Pump Off): 290 ml. <br />5. Step -through time to full flow 2 seconds (0 psi. to full pump pressure, no leak) <br />6. Leak detector stays in Leak Search Position with a 3 GPH leak - Yes: X PASS No: FAIL <br />7. Was the leak detector adjusted — Yes: No: X <br />Symptoms <br />1. Won't find 3 GPH leak: 2. Stays in Slow Flow: <br />3. Other: <br />************ If This Unit Is Returned Under Warranty Please Complete The Following *********** <br />Vaporless RGA#: Return By (Company): <br />Telephone: Contact: <br />Customer Control : Address: <br />City: State: Zip: <br />(See Website - www.vaporless.com. - Technical Bulletin 032805) <br />