Laserfiche WebLink
MOITOR SYSTEM CERTIFICAODN <br /> TANNOLOOY <br /> Test Date: 06/09/2000 Work Order#: 2212405 <br /> Client: CHEVRON,U.S.A. Site: CHEVRON 201761 <br /> P.O.BOX 6004 1103 S.MAIN ST. <br /> SAN RAMON,CA,94583 MANTECA, CA,95337 <br /> Overall System Operation <br /> The pumps; Shut down automatically if the system detects a leak,fails to operate,or is <br /> electronically disconnected. [X ] Yes ( ] No <br /> The system has functioning audible and visual alarms. (X ] Yes ( ] No <br /> The circuit breaker for the system is properly identified. (X ) Yes [ ] No <br /> The system is certified operational per manufacturer's performance standards. (X ] Yes ( l No <br /> Product Tank Monitoring: [X ] Double wall [ ] Single wall <br /> Make: VEEDER-ROOT Model: LIQUID <br /> Type: ANNULAR SPACE.L.IQUIID How many: 3 Operational: (X ] Yes [ l No <br /> (.Automatic tank gauge,annular space vapor probe,annular space liquid probe,hydroguard system, <br /> vadose zone monitor well,groundwater monitor well) <br /> Comments: <br /> 3 Automatic Tank Guages operational <br /> Product Piping Monitoring: [X ] Double wall ( l Single wall <br /> Make: VEEDER-ROOT Model: PLLD <br /> Type: ELECTRONIC LINE: How many: 3 Operational: IX ] Yes [ ] No <br /> (Piping sump liquid sensor,piping trench liquid sensor,electronic line pressure sensor, <br /> mechanical line leak detector) <br /> Comments: <br /> 3 Sump Sensors operational <br /> Other Monitoring Systems: <br /> Make: VEEDER-ROOT Model: LIQUID <br /> Type: SUMP LIQUID SENSOR How many: 6 Operational: [X ] Yes [ ] No <br /> Comments: <br /> Technician: MICHAEL T . V .4QUE Technician Signature: <br />