Laserfiche WebLink
PEI/ 1z -1 0 <br /> A UST system component or dispenser that is leaking resp® procedure specified by the facility owner or <br /> fuel or vapor should not remain in service.If a leak is operator. A spill kit should be readily available at the <br /> discovered, deactivate the system or component, label facility. <br /> it"Out of Service" and notify the appropriate person. Avoid igniting spilled fael. Immediately remove people <br /> 3.5 People Hazards. Other personnel present ata from the area and verify that no open flames orother <br /> facility may cause significant hazards.Customers operat- ignition sources are in the area of the spill.Do not allow <br /> ing vehicles,facility managers or operators who re-ener- the starting of vehicles in the area. <br /> gize electrical circuits that have been tamed off,or clerks Handle and dispose of used spill cleanup and sorbent <br /> who authorizes at dispensers that are being serviced materials a=ording to instructions provided by the owner <br /> are hazards that must be anticipated and addressed, or operator of the facility. Do not store contaminated <br /> Always advise personnel in charge of point-of-sale sys- materials inside a building. <br /> to and the facility management of work to be done. <br /> Take note of traffic patterns. No the activities of any The owner or operator should report any spill or discharg- <br /> other workers at the facility and discuss with them ways es to the authority having jurisdiction (AHJ) as required <br /> of minimng orelimmating any hazards that may be by law. In some locations, reporting to more than one <br /> presented by their activities. authority may be required. <br /> Use traffic barriers,personal protective equipment,lock- 3.10 Vehicle Hazards. Vehicles can present one of the <br /> out/ out procedures, fuel shutoff valves and PUMP more serious and common safety hazards while working <br /> electrical disconnects as necessary to ensure safety dur- at dispenser islands and areas where traffic is present at <br /> ing dispenser and tank system inspection, testing and UST facilities.Drivers often are distracted and inattentive <br /> maintenance activities. at UST facilities, and may not notice personnel conduct- <br /> ing testing,maintenance or repair activities. <br /> 3.6 Test Equi prnent. Use equipment intended for test- <br /> ing spill, overfill, leak detection and secondary contain- Take appropriate safety precautions prior to performing <br /> mant equipment- any inspection, testing or maintenance of overfill, leak <br /> detection and release prevention equipment <br /> For tests that impose a vacuum on a containment volume Workers should wear high-visibility safety-vests while <br /> or interstitial space, use only an air-operated vacuum working in areas where vehicle traffic may be present <br /> source or a vacuum pump powered by an explosion- <br /> proof motor. Vacuum pumps with electric motors that Use safety cones,barricades,warning sign g and/or barrier <br /> are not explosion-proof may ignite,flammable vapors, If tape to designate and isolate work areas. Take care not to <br /> a portable air compressor is used, it should be located at place tools or equipment outside the designated area. Do <br /> least 20 feet away from the venturi-eductor or outside any not remove safety equipment,barricades or signs until all <br /> Class 1,Division I area. work is completed and equipment is ready to be returned <br /> to service, <br /> 3.7 Confined Spece Entry. UST system containment <br /> sumps may be large enough to present hazards associated <br /> with confined space entry. Refer to OSHA 1910,146 for <br /> further guidance on confined space entry procedures. <br /> 3.8 Use of Water Versus Product for Testing. Do 4. TANK SECONDARY <br /> not use gasoline, gasolinelethanol blends, diesel fuel or CONTAINMENT INTEGRITY <br /> other stored liquids to test the integrity of spill buck- TESTING <br /> ets and containment sump walls. Use water orother <br /> approved monitoring liquid for tests requiring a test liq- <br /> uid.A release of product from a leaking system presents 4-1 General. Double-walled tanks have interstitial <br /> a safety hazard and could cause environmental damage. spaces that can be tested for integrity. <br /> Follow the guidelines in Section 6.7 for proper disposal There are two methods for testing the integrity of tank <br /> of water used in tee tin& secondary containment systems®dry and wet. Dry test <br /> methods use a partial vacuum to determine the integrity <br /> 3.9 Responding to Spills. Spills may occur during of the containment To perform a wet test on an existing <br /> maintenance,testing or repair activities. Follow the sPill liquid-filled tank interstitial space,the liquid level in the <br /> 0 pei.org <br />