Laserfiche WebLink
s a Page 2 of 9 <br /> 1. TANK ANNULAR TESTING <br /> Test Method Developed By: ❑Tank Manufacturer ®Industry Standard ❑Professional Engineer <br /> []Other(Spec) <br /> Test Method Used: ❑Pressure ®Vacuum ❑Hydrostatic <br /> ❑Other(Specify) <br /> Test Equipment Used: See attached testing procedures Equipment Resolution: <br /> Tank#87-1 Tank# 87-2 Tank#91 Tank# <br /> Is Tank Exempt From Testmg?' ❑Yes ®No ❑Yes ®No ❑Yes ®No ❑Yes ❑No <br /> Tank Capacity: <br /> Tank Material: Fiberglass Fiberglass Fiberglass <br /> Tank Manufacturer: <br /> Product Stored: 87 Gas 87 Gas 91 Gas <br /> Wait time between applying <br /> pressure/vacuum/water and 15 nunutes 15 minutes 15 minutes <br /> starting test: <br /> Test Start Time: 9:31AM 9:07AM 8:21AM <br /> Initial Reading(Rj): 10"HG 10"HG 10"HG <br /> Test End Time: 10:31AM 10:07AM 10:21AM <br /> Final Reading(RF): 10"HG 10"HG 10"HG <br /> Test Duration. 1 hour 1 hour 1 hour <br /> Change in Reading(RF-RI): 0 0 0 <br /> Pass/Fail Threshold or Criteria: 0.00 0.00 0.00 0.00 <br /> Was sensor removed for testing? ❑Yes®No RNA ❑Yes®No[:INA ❑Yes®No[:INA ❑Yes®No[INA <br /> Was sensor properly replaced and <br /> verified functional after testing? ❑Yes❑No®NA [:]Yes❑No®NA ❑Yes❑No®NA ❑Yes[]No®NA <br /> Comments—(include information on repairs made prior to testing, and recommended follow-up for failed tests) <br /> ' Secondary containment systems where the continuous monitoring automatically monitors both the primary and secondary <br /> containment,such as systems that are hydrostatically monitored or under constant vacuum,are exempt from periodic containment <br /> testing. {California Code of Regulations,Title 23,Section 2637(a)(6)) <br />