Laserfiche WebLink
0 <br /> 1115000 Field Test Apparatus Page 1 of 1 <br /> JgTanknology Line Leak Detector Test <br /> Work Order: 2304993 Date:_5/25/2012 <br /> Site Name/ ID: CHEVRON 201761 / 201761 <br /> Address: 1103 S. MAIN ST. PERMIT NUMB. N-3315 <br /> City: MANTECA State: CA Zip: 95337 <br /> Tank ID 1 3 <br /> Product SUPREME REGULAR <br /> Product Line 1 1 <br /> Tested From 9 9 <br /> Existing/New Existing Existing <br /> Mechanical/Electronic Electronic Electronic <br /> Manufacturer/Model Veeder Root PLLD Veeder Root PLL <br /> Serial No. 016543 015610 <br /> Pump Operating Pressure(psi) 40.00 37.00 <br /> Calibrated Leak(mi/min) 189.0 189.0 <br /> Calibrated Leak(gph) 3.00 3.00 <br /> Holding PSI 20.00 20.00 <br /> *N/A for Electronic LD's <br /> Resiliency(ml) <br /> *N/A for Electronic LD's <br /> Metering PSI <br /> *N/A for Electronic LD's <br /> Opening Time(sec) <br /> *N/A for Electronic LD's <br /> Test Results Pass Pass <br /> Technician Comments: <br /> Technician Name: Steven Willl1lems Certification#: 1931 <br /> Technician Signature: <br /> Environmental Compliance for Petroleum Systems <br /> ®2010 Tanknology Inc.,Austin,TX. All rights reserved. tanknology.com <br />