Laserfiche WebLink
SM JOAQUPA COUNTY <br /> EWRONMENTAL HEALTH DEPARTMENT <br /> Wo LeaL Main ls"*�Stockton,Calftv"05=-3029 <br /> TeleOMW{249} ;(209). - .i. <br /> CONTINUATION4 <br /> -.01/21/11 <br /> ill` : 1103 S Main Street Manteca <br /> SUMMARY Of T <br /> 1,_CUMS 9,w 1111MR-Notice to cam <br /> UST Inspection Report <br /> 10 & 1 . The 87 Tank 1 and 2 and the 91Tank annular sensor failed to activate an audible and visual <br /> alarm due to the monitoring panel net being operational, therefore, the tank is not monitored. The <br /> interstitial space shall be monitored with a monitoring system connected to an audible and visual alarm <br /> system, Immediately contact a properly licensed, trained, and certified contractor to replace the failed <br /> component with a functional component(LG 113-x listed, if applicable) under permit and inspection of <br /> the E D within one business day. If unable to establish continuous monitoring of the UST systemcease, <br /> operation and remove fuel from all the tanks. <br /> 13_ All the under dispenser containment sensor and the STP sump sensors for the 87 Tank 1 and 2 and <br /> 91 Tank failed to activate an audible and visual alarm to ensure Continuous monitoring of the tank <br /> system due to the monitoring panel not being operational. All n°monitohng equipment shall be maintained <br /> to activate an audible and visual alarm or stop the flow of product at the dispenser when it detects a <br /> leak. Correct immediately by having a properly licensed,trained, and cerfified coniactor replace the <br /> failed component with a functional component(LG 113®x listed,if applicable) and obtain a permit within <br /> 1 business day from the EHD. If the failed component can't be replaced immediately,there is a <br /> possibility that the 87 Tank 1 and 2 and 91 Tank UST system may be red tagged to prevent fuel inputs. <br /> 17. The 87 and 91 turbine electronic line leak detector failed to detect a leak due to the monitoring panel <br /> not being operational. All line leak detectors shall be rapable of detecting a 3-gallon per hour leak at 1 <br /> psi. Immediately have a properly licensed, trained, and certified contractor repair or replace the failed <br /> leak detector(LG 113-x listed, if applicable) and obtain a permit within one business day from the EH D. <br /> If the failed leak detectorcan't be replaced immediately,there is a possibility that the 87 and 91 UST <br /> system may be red tagged to prevent fuel inputs- <br /> 21. Liquid was observed in the 87 fifl sump on Tank 1 and 2. If water could enter into they secondary <br /> containment by precipitation or infiltration, it must be removed and lsp Ad of properly. Immediately <br /> remove,this liquid. make a hazardous waste determination per Title 22 hazardous waste regulations, <br /> and manage it accordingly. Ensure that the 87 fill sump on Tank 1 and 2 Is maintained free of liquid. <br /> The technician removed the liquid and put it in the facility's hazardous waste storage container. <br /> LAU.P-M STMF'nWASS=AMWOTHFAIUNOMCCOPLYRYUC AgM MOM ORM WOU SE WUjW AT 7M CMMff HOURLY RATE($122). <br /> YMS E Cit_ t T Y TIME T E HOURLY RATL <br /> CONTINJAnmFoRm <br /> Q(10 <br /> 90/00 39VJ NONt gHO T99T ZZ-'9T TT9Z/TZ/Tg <br />