Laserfiche WebLink
0 REC IVED <br /> SANJOANIN JAN 6 2018 <br /> Environmental Health Department <br /> _ .. U T . ....w,. <br /> T 0 HEALTH <br /> Facility Narne: Facility Add a: D <br /> CHEVRON USA#201761" 1103 S MAIN ST,MANTECA January 04,2018 <br /> ftern 0 Remarks <br /> 318 CCR 2636(0(2)Leak detector failed to detect a 3.0 gph leak at 10 psi, <br /> The 87 octanes VMl line leak detector failed to detect a leak when tested All line leak detectors shall be capable of <br /> detecting a3-gallon per hour leak at 10 psi The service technician replaced both of the siphon jet valves on the two <br /> 87 tanks,retested it,and it passed. <br /> This was corrected on site. <br /> This is a minor violation <br /> Overall Inspection Comments: <br /> Complete and submit a copy of the Return to Compliance Certification form to the EHD with a statement <br /> documenting the corrective actions that have been or will be taken for each violation, and any supporting <br /> paperwork, by February 3,2018. <br /> Documents reviewed during inspection:Alarm history and sensor set up,operating permit,monitoring plans, <br /> response plan, financial responsibility and letter from chief financial officer,employee training log,designated <br /> operator statement,designated operator monthly reports,monitoring system certification reports(2015, 2016, <br /> 2017), secondary containment testing report(2015), <br /> Documents received by operator: Return to compliance certification form,routine inspection report, on-site <br /> retrofit verification inspection report. <br /> Note When it fails,the diesel spill bucket shall be replaced with a spill bucket that has a minimum capacity of 5 <br /> gallons,is protected from galvanic corrosion,and has either a drain valve which allows drainage of the collected <br /> spill into the primary container or provide a means to keep the spill container empty pursuant to CCR Title 23, <br /> section 2635(b)(1), <br /> Please be aware that as of January 1, 2014,facility operators are required to upload the following UST program <br /> documents into the California Environmental Reporting System(CES): UST Monitoring Site Plan, UST <br /> Certification of Financial Responsibility,UST Response Plan, UST Letter from Chief Financial Officer(if <br /> applicable),and the Owner Statement of Designated Operator Compliance, The USTOwner/Operator:Written <br /> Agreement,if applicable,can be stored at the facility or uploaded into CS. <br /> AFTER THE COMPLIANCE DATE,EHD WILL BILL FOR ALL TIME AND ACTIVITIES ASSOCIATED WITH BRINGING <br /> IS FACILITY BACK INTO COMPLIANCE, <br /> THIS FACILITY IS SUBJECT TO REINSPECTION AT ANY TIME AT EHD'S CURRENT HOURLY RATE, <br /> R Ived try. D : January 04,2018 Inspector Ina r Phone: <br /> Printed Name and BETTY HO,EH Specialist (209)468-3455 <br /> L—Apry Loisa Verduzco,Manager <br /> FA0004521 PRO232587 Scoot omw2ota <br /> EHD 23-01 Ray 10/31/2017 Page 4 of 4 U star Tar*Program OR <br /> 1868 E Hazelton Avenue I Stockton,California 952051 T 209 468-3420 1 F 209 464-0138 1 www sjcehd corn <br />