Laserfiche WebLink
0 • <br /> LDT 5000 Field Test Apparatus Page 1 of 1 <br /> Tankno�ogy Line Leak Detector Test <br /> Work Order: 2334167 Date: 1/4/2018 <br /> Site Name/ID: CHEVRON 201761 /201761 <br /> Address: 1103 S. MAIN ST. PERMIT NUMB. N-3315 <br /> City: MANTECA State: CA Zip: 95337 <br /> Tank ID T1 Supreme T3 Regular 1 T3 Regular 1 <br /> Product SUPREME REGULAR REGULAR <br /> Product Line 1 1 1 rn VON- JJ <br /> Tested From 11 11 11 <br /> Existing/New Existing Existing Existing 1� <br /> Mechanical/Electronic Electronic Electronic Electronic <br /> Manufacturer/Model Veeder Root PLLD Veeder Root PLLD Veeder Root PLLD ^, HEALT <br /> Serial No. 404907 015618 015618 EN T IFNt <br /> Pump Operating Pressure(psi) 29.00 29.00 29.00 <br /> Calibrated Leak(ml/min) 189.0 189.0 189.0 <br /> Calibrated Leak(gph) 3.00 3.00 3.00 <br /> Holding PSI <br /> N/A for Electronic Lo's <br /> Resiliency(ml) <br /> N/A for Electronic Lo's <br /> Metering PSI <br /> NIA for Electronic LD's <br /> Opening Time(sec) <br /> N/A for Electronic Lo's <br /> Test Results Pass Fail Pass <br /> Technician Comments:initial testing on regular leak detector failed siphon jet valve on both regular turbans were replaced, <br /> 50 gallons of product was purged and testing passed. <br /> Technician Name: Jarrod Cooke Certification#: 2081 <br /> Technician Signature: Expire Date: 2/24/2019 <br /> Environmental Compliance for Petroleum Systems <br /> ©2018 Tanknology Inc.,Ausfin,TX. All rights reserved. tanknology.com <br />