-rLTA I VK-TEK <br /> R PRESSURIZED PIPING LEAK DETECTION CERTIFICATION SHEET <br /> Date: OCT 10,2008 Work Order# 08101001-2 <br /> Location: RAMOS OIL Contact: DAVE NELSON <br /> 10842 S.HARLAN ROAD <br /> FRENCH CAMP, CA 95231 Telephone: (916)371-3289 <br /> SUMP# 1 1 <br /> PRODUCT DIESEL DIESEL <br /> LD TYPE Mechanical, (W)PLLD, (P)LLD I M M <br /> LD MANUFACTURER REDJACKET VAPORLESS <br /> LD MODEL FXIOV LD 2000 <br /> LD SERIAL NUMBER 788 06011650 <br /> SUMP CONDITION DRY DRY <br /> RESILIENCY 100 ML 80 ML <br /> OPERATING PRESSURE 28 PSI 28 PSI <br /> OPENING TIME .0246 SEC .0339 SEC <br /> METERING PRESSURE 10 PSI 10 PSI <br /> FUNCTIONAL ELEMENT HOLDING PRESSURE 8 PSI 18 PSI <br /> LEAK RATE LD DETECTED 3 GPH 3 GPH <br /> DOES LD DETECT 3 GPH LEAK RATE? YES YES <br /> DOES VEEDER-ROOT CONSOLE ALARM? N/A N/A <br /> LD PASS OR FAIL? PASS PASS <br /> Comments: <br /> Technician: Robert Neimeyer Contractor Lic. # 803705 <br /> Signature: <br /> TANK-TEK ENVIRONMENTAL CORPORATION <br /> 607 Elmira Road, PMB 336,Vacaville, CA 95687 — Ph.(707)446-6151 - Fax (707)446-6192 - E-mail:tank-tek@cwnet.com <br /> 31828 Cercle Chambertin,Temecula, CA_ 92591 — Ph.(951)699-8058 - Fax(951)699-8059 - E-mail:drbtanktek@sdccu.net <br />