Laserfiche WebLink
Return to compliance S. Harlan <br /> Item 104:Tank manufacturer was changed in CERS from Xerxes to containment solutions <br /> Item 105:Tank monitoring plan was changed in CERS from ATG leak detection to reflect the site that is <br /> using the annular sensor for leak detection on the tank. The leak detection for the piping was changed <br /> to continuous monitoring using the VR208 sensor in the turbine sumps.The leak detector was changed <br /> from LD2000 to 99LD2000.Joy Kachadorian was removed from CERS and replaced with Lauren Takos. <br /> Item 201:All paperwork for the previous three years has ben copied and left onsite. <br /> Item 215: current permit to operate has been left onsite. <br /> Item 310: sensor L5 was not included in shut down of the diesel turbine. Sump was found to be dry on <br /> inspection and programing was changed to include L5 on the shutdown of the diesel turbine. L5 was <br /> tested post programing change and functioned properly. <br /> Best Regards <br /> Steven Richardson. <br />