Laserfiche WebLink
APR-30-2010 FRI 05: 45 I'M P. 045 <br /> 04/2812010 13:26 661393a* CHUCK HILL PAGE 06/07 <br /> EPIC Compliance Systems, LLC <br /> 10M 86YOM SUR--150-53n Swe,CA 94C6S-ConnC1*rL[r-*aEN3430 <br /> MECHANICAL LEAK DETECTOR TEST DATA SHEET <br /> Site Name — LrA;y Truck Ston <br /> Site Address, 3940 N Tracv Blvd Trac CA 95304 <br /> Test Information <br /> 2 3 4 <br /> Product 87 91 carside Diesel West Histo East HFIo <br /> Manufacturer VM1 VMI VM1 VMI VMI <br /> Model 99 LD2000 99 LD2000 99 1-132000 LD 3000 LD 3000 <br /> Resiliency 200 ml 110 MI 75 ml N/A - <br /> Opening Time 2 sec 3 Sac 3 sec 17 sec <br /> Test Leak Raft(ml/min)9ph 3 GPM 3 GPM 3 GPM 3 GFIH 3 GPH <br /> Metering PSI 22/..32 17/27 17/32 21135 <br /> L PASS I FJAU1 pass pwcm pass pass Fal I <br /> L <br /> Comments: <br /> This lethr ceriffies that the leak detector test(s) were performed at the above referenoW facility according to the <br /> equipment manufacturers proceftras and limi1aflons and the results as Usted are to my knowledge tve and correct. <br /> The mechanical leak detacw test passnail is determined using a low flow threshold trip rate of 3 gph at 10 PSI. <br /> Inspected By., EPIC Compliance Systems, LLC <br /> Technician: kefth Hjj n Signature: <br /> Date, 010 rrme: <br />