Laserfiche WebLink
EPIC Compliance Systems, LLC <br /> P Y <br /> c G�4C <br /> SYSTEMS CE 1001 Bayhill Dr,Suite 150■San Bruno,CA 94066■Contractor Lic.#880430 <br /> 888-700-EPIC.Fax 415-296-6110•www.epiccompliance.com <br /> MECHANICAL LEAK DETECTOR TEST DATA SHEET <br /> Site Name Tracy Truck Stop Date 04/02/2010 <br /> Site Address 3940 N Tracy Blvd Tracy, CA 95304 <br /> Test Information <br /> 1 2 3 4 5 <br /> Product 87 91 Carside Diesel West HFIo East HFIo <br /> Manufacturer VMI VMI VMI VMI VMI <br /> Model 99 LD2000 99 LD2000 99 LD2000 LD 3000 LD 3000 <br /> Resiliency 200 ml 110 ml 75 ml N/A - <br /> Opening Time 2 sec 3 sec 3 sec 17 sec - <br /> Test Leak Rate(ml/min) gph 3 GPH 3 GPH 3 GPH 3 GPH 3 GPH <br /> Metering PSI 22/32 17/27 17/32 21/35 - <br /> PASS/ FAIL Pass Pass Pass Pass Fail <br /> Comments: <br /> This letter certifies that the leak detector test(s) were performed at the above referenced facility according to the <br /> equipment manufacturers procedures and limitations and the results as listed are to my knowledge true and correct. <br /> The mechanical leak detector test pass/fail is determined using a low flow threshold trip rate of 3 gph at 10 PSI. <br /> Inspected By: EPIC Compliance Systems, LLC <br /> Technician: Keith Huston Signature: <br /> Date: 04/02/2010 Time: - <br />