Laserfiche WebLink
0 0 <br /> Probe and Sensor Installation Probe and Sensor Installation Diagrams <br /> Brackets,clamp,etc., Weatherproof junction box with 1/2-inch N.P.T. <br /> from Universal sensor threads(16 cubic inch volume minimum). <br /> mounting kit <br /> Seal-off <br /> U-channel <br /> Cord grip <br /> Rubber grommet seal <br /> clamped on inside- <br /> ® <br /> J J or as recommended by <br /> J J dispenser pan manufacturer. <br /> 1/2"Rigid conduit <br /> Dispenser pan sensor to console <br /> sensorsWpsinsteps �,,,, '�' <br /> Dispenser pan <br /> "Dispenser pan sensor should: <br /> 1. Rest in the cup or the lowest point of the dispenser pan. <br /> 2. Be positioned so as to be removable when pulling the sensor straight up out of the pan. <br /> 3.Be mounted in a true vertical position. <br /> Rem J.-Typical Dispenser Pan Sensor Installation <br /> „ U-channel <br /> Brackets,clamp,etc.,from <br /> Universal sensor mounting kit <br /> Cord grip Weatherproof junction box with <br /> 1/2-inch N.P.T.threads(16 cubic <br /> Product line 10 inch volume minimum). <br /> Dispenser Seal-off <br /> containment Rubber grommet seal <br /> sump clamped on inside- <br /> or as recommended by <br /> ® dispenser pan manufacturer. <br /> 1/2"Rigid conduit <br /> to console <br /> Dispenser pan sensor <br /> sensors\dispscin.eps <br /> "Dispenser pan sensor should: <br /> 1. Rest in the cup or the lowest point of the dispenser containment sump. <br /> 2. Be positioned so as to be removable when pulling the sensor straight up out of the pan. <br /> 3. Be mounted in a true vertical position. <br /> Item K.-Typical Dispenser Pan Sensor Installation in a Containment Sump <br /> Figure 5. TLS-350 Probe and Sensor Installation Diagrams-cont'd. <br /> 21 <br />