Laserfiche WebLink
Connecting Wiring to Power Area Modules 4-Re2y Output Module <br /> Connecting iri r Area Modules <br /> Figure 1 on page 6 lists the permissible Power Area modules. <br /> 4-Relay Output Module <br /> The 4-Relay Output Module incorporates four Form-C relay outputs and the I/O <br /> Combination Module incorporates two Form-C relay outputs. <br /> Important Output Relay Connection Restrictions <br /> 1. Do not connect output relays to a device that draws more than 2 amperes of <br /> current.Output power:output relay contact,resistive load- 120 Vac,2 A max.;or <br /> 24 Vdc,2 A max. <br /> 2. Alarm relays cannot be used for flow control.Alarm relays provide only a <br /> momentary closure and cannot actuate flow control devices such as valves and <br /> pump motor relays for extended periods of time. <br /> Connect the wires from each external device to the appropriate terminals on the output <br /> module [see Figure 17]. <br /> RELAY I—t_1 T2-2—i—s—sT4—a <br /> NC NO C NC NO C NC NO C NC NO C I RELAY RATINGS <br /> Form C Contacts <br /> 120 VAC,2A Max;or <br /> ® ® ® ®® ® ® ®El E1 L1 0 0-1-11111m _••® 24 VDC,2A Max. <br /> -4-fELAY OUTPUT <br /> Rigid Conduit <br /> (enters Console '\ Console <br /> through a �� - ----------- - -� ��// <br /> Power Area Up to 4 <br /> knockout) external <br /> devices <br /> NC NO C NCCNO/C <br /> W <br /> External External <br /> Device Device <br /> consolesWOmw.eps <br /> Figure 17. 4-Relay Output Module Wiring <br /> 43 <br />