Laserfiche WebLink
Appendix Wiring Record - Intrinsically Safe Area <br /> The wiring record forms in this appendix are intended for the installer's use to <br /> accurately record the wiring scheme and wiring identification for probes and sensors <br /> connected to the TLS-350 or TLS-350R Console.A definition of each record heading <br /> is given below. <br /> CAUTION: Failure to identify and maintain the relationship of wiring between <br /> probe and sensor locations and their positions on console module connectors <br /> could result in the incorrect identification of a leak type or leak location, or <br /> improper system operation. It is critical that you properly identify, record, and <br /> maintain these wiring relationships. <br /> Module Position-The slot in the intrinsically safe area of the console where this <br /> module is installed. (See the Circuit Directory located on the inside of the console's <br /> right-hand door.) <br /> Module Type-Enter the type of module installed in this slot,i.e.,Probe#1,Vapor <br /> Sensor-NW Corner. <br /> Probe/Sensor Identification-Identify the device connected to this module location, <br /> i.e.,Tank#1 Probe,Vapor Sensor-NW corner. <br /> NOTE:Probe modules have 4 positions,interstitial sensor modules have 8 positions, <br /> and vapor modules have 5 positions. <br /> Terminal Identification-Probe and interstitial sensor connectors have 2 terminals per <br /> probe or sensor position(+and—).Vapor sensor,groundwater sensor,and Type B <br /> sensor connectors have 3 terminals per sensor. <br /> Color Code or Marking-Enter the color or marking that identifies the probe or <br /> sensor wire connecting to this module terminal. <br /> A-1 <br />