0 0 Page dof <br /> 9. SPILL/ ILL CONTAINMENT BOXES <br /> Facility is Not Equipped With Spill/Overfill Containment Boxes 0 <br /> Spill/Overfill Containment Boxes are Present,but were Not Tested [I <br /> Test Method Developed By: n Sump Manufacturer 0 Industry Standard 0 Professional Engineer <br /> 0 Other(Specify) <br /> Test Method Used: 0 Pressure 0 Vacuum 0 Hydrostatic <br /> [I Other(Specify) <br /> Test Equipment Used: INCON TS.STS UNIT Equipment Resolution: <br /> Fill Sump#87 F. Fill Sump#87 V. Fill Sump# Fill Sump# <br /> Bucket Diameter: 12 INCH 12 INCH <br /> Bucket Depth: 15 1/2 INCH 151/21NCH <br /> Wait time between applying <br /> pressure/vacuum/water and 30 MINUTES 30 MINUTES <br /> starting test: <br /> Test Start Time: 9:08 9:25 AM 9:08 AM 9:25 AM <br /> Initial Reading(RI): 7.7487 7.7489 7.1264 7.1263 <br /> Test End Time: 9:23 AM 9:40 AM 9:23 AM 9:40 AM <br /> Final Reading(RF): 7.7488 7.7489 7.1263 7.1263 <br /> Test Duration: 2X 15 2X 15 2X 15 2X 15 <br /> MIN MIN MIN NUN <br /> Change in Reading(RF-R,): .0001 .0000 -.0001 .0000 <br /> Pass/Fail Threshold or Criteria: .002 .002 .002, .002 <br /> am: .-OFail <br /> Test Res ❑ Pus P 0 Pus:, OFA <br /> Comments— (include information on repairs made prior to testing, and recommended follow-up for failed tests) <br /> * BOTH 87 SPILL BUCKETS PASSED HYDROSTATIC TEST. NO REPAIRS <br /> ARE NEEDED AT PRESENT TIME. <br />