VM1 <br /> Vaporless Manufacturing, Inc. <br /> Quality Petroleum Equipment <br /> Solutions for Over 20 Years <br /> LDT-890 Test Form&VMI Warranty Checklist <br /> October I,2006 <br /> Test Information <br /> Date: 11/25/08 Test Company: EPIC Compliance Systems. Inc. <br /> Telephone: 209-825-0332 Contact : Ricky <br /> Site I.D: Gas Depot Address: 1330 E. Yosemite Ave <br /> City: Manteca State: CA Zip: 95336 <br /> Type of Test Equipment: LDT-890 <br /> Submersible Pump Identification <br /> MFG: FE PETRO Model No: 1 STR2-00 Serial No: 99121417 <br /> Leak Detector Identification <br /> MFG: VMI Model No: 99 LD 2000 Serial No: UNK <br /> Replacement Leak Detector Identification <br /> MFG: Model No: Serial No: <br /> Line Conditions <br /> 1.Type of Pipe: FG 2.Diameter of Pipe: 2" 3.Length of Pipe: 100' <br /> 4.Burial Depth of Leak Detector: 30" 5.Kind of Fuel: Diesel 6.Date of Last Line Test: <br /> Test Conditions <br /> 1.Operating Pump Pressure: 38 2.Gallon per hour test rate: 3 @ 10 psi <br /> 3.Static Line Pressure(Pump Off): 38 4.Bleedback Test(Pump Off): 1100 ml. <br /> 5.Step-through time to full flow 3 seconds(0 psi.to full pump pressure,no leak) <br /> 6.Leak detector stays in Leak Search Position with a 3 GPH leak-Yes: X PASS No: FAIL <br /> 7.Was the leak detector adjusted—Yes: No: X <br /> PLLD shut down line when leak was detected Pass <br /> Symptoms <br /> 1.Won't find 3 GPH leak: 2.Stays in Slow Flow: <br /> 3.Other: <br /> ************ If This Unit Is Returned Under Warranty Please Complete The Following *********** <br /> Vaporless RGA#: Return By(Company): <br /> Telephone: Contact: <br /> Customer Control#: Address: <br /> City: State: Zip: <br /> (See Website-www.vapariess.com -Technical Bulletin 032805) <br />