11 <br />SWRCB, January 2006 <br />Spill Bucket Testing Report Form <br />This form is intended for use by contractors performing annual testing of UST spill containment structures. The completed form and <br />printouts from tests (f applicable), should be provided to the facility owner/operator for submittal to the local regulatory agency. <br />1. FACILITY INFORMATION <br />Facility Name: Gas Depot 2 Date of Testing: 12/18/2013 <br />Facility Address: 1330 E. Yosemite Ave. Manteca, Ca. 95336 <br />Facility Contact: Kevin Phone: (209) 825-03 <br />Date Local Agency Was Notified of Testing: 0q - i 3 tr <br />Name of Local Agency Inspector (tfpresent during testing): Aris Cacapit <br />2. TESTING CONTRACTOR INFORMATION <br />Company Name: Reliable Petroleum Services, Inc. <br />Technician Conducting Test: Guadalupe Sanchez° rtti <br />Credentials': x CSLB Contractor x ICC Service Tech. ❑ SWRCB Tank Tester ❑ Other (Spec) <br />License Number(s): 883706 5250451 -UT <br />3. SPILL BUCKET TESTING INFORMATION <br />Test Method Used: xHydrostatic ❑ Vacuum ❑ Other <br />Test Equipment Used: Standard Tape Measure <br />Equipment Resolution: N/A <br />Identify Spill Bucket (By Tank <br />Number, Stored Product, etc) <br />1 T1: 87 Fill <br />2 T2: 91 Fill <br />3 T3: Diesel Fill <br />4 T4: <br />Bucket Installation Type: <br />Direct Bury <br />x Contained in Sump <br />Direct Bury <br />x Contained in Sump <br />Direct Bury <br />x Contained in Sump <br />Direct Bury <br />Contained in Sum <br />Bucket Diameter: <br />12" <br />12" <br />12" <br />Bucket Depth: <br />13 3/4" <br />13''/2" <br />171/4" <br />Wait time between applying <br />vacuum/water and start of test: <br />1 minute <br />1 minute <br />1 minute <br />Test Start Time (TI): <br />12:05 p.m. <br />12:05 p.m. <br />12:05 p.m. <br />Initial Reading (Ri): <br />11 5/8" <br />11 3/4" <br />143/4 " <br />Test End Time (TF): <br />1:05 p.m. <br />1:05 p.m. <br />1:05 p.m. <br />Final Reading (RF): <br />11 5/8" <br />11 3/4" <br />143/4 <br />Test Duration (TF— TI): <br />1 hr <br />lhr <br />1 hr <br />Change in Reading (RF- RI): <br />0 <br />0 <br />0 <br />Pass/Fail Threshold or <br />Criteria: <br />1/16" <br />1/16" <br />1/16" <br />Test Result: <br />x Pass ❑ Fail <br />x Pass ❑ Fail <br />x Pass ❑ Fail <br />Pass ❑ Fail <br />Comments — (include information on repairs made prior to testing, and recommended follow-up for failed tests) <br />CERTIFICATION OF TECHNICIAN RESPONSIBLE FOR CONDUCTING THIS TESTING <br />I hereby certify that all the information contained in this report is true, accurate, and in full compliance with legal requirements. <br />Technician's Signature: � <br />� Date 12/18/2013 <br />' State laws and regulations do not currently require testing to be performed by a qualified contractor. However, local requirements <br />may be more stringent. <br />