Laserfiche WebLink
PUBLIC H?ALTH SERVIAS <br />SAN JOAQUIN COUNTY <br />ENVIRONMENTAL HEALTH DIVISION <br />Karen Furst, M.D., M.P.H., Health Officer <br />304 East Weber Avenue, Third Floor • Stockton, CA 95202 <br />209/468-3420 <br />MEMORANDUM <br />Date: September 7, 2000 <br />To: Steve Scheman OL <br />From: Michael Kith, Sr. REHS <br />San Joaquin County <br />Environmental Health Division (EHD) <br />Re: Hammer Lane Tesoro, 3304 Hammer Ln, Stockton. <br />Your application for permit to install new underground storage tank (UST) has been <br />approved with the following conditions: <br />1. Contact Fire Department for permit. <br />2. All new submittals supercede the previous ones. <br />3. Automatic pump -shutdown must satisfy all conditions listed in CCR 2636(g). <br />4. Overfill prevention device, OPW 61 SO -410C, shall be installed at 90% of tank <br />volume in order to achieve a total shut -down at 95%. <br />5. Submit certification of financial responsibility and letter from chief financial officer <br />to EHD prior to scheduling tank setting appointment. <br />6. Contact Michael Kith for inspection. See New UST Installation Inspection Record <br />for the required inspection. All appointments must be scheduled at least 48 hours in <br />advance. <br />7. Please be informed that SB 989 may require secondary containment on all vapor <br />return lines in future. <br />8. Permit expires at the end of calendar year. <br />If you shall have any questions please contact me at 209-468-3444. <br />A Division of San Joaquin County Health Care Services <br />