Laserfiche WebLink
SWRCB, January 2002 <br />0 Page 2of2 <br />Secondary containment systems where the continuous monitoring automatically monitors both the primary and secondary <br />containment, such as systems that are hydrostatically monitored or under constant vacuum, are exempt from periodic containment <br />testing. (California Code of Regulations, Title 23, Section 2637(a)(6)) <br />4. TANK ANNULAR TESTING <br />Test Method Developed By: <br />X Tank Manufacturer ❑ Industry Standard ❑ Professional Engineer <br />❑ Other (Specify) <br />Test Method Used: <br />❑ Pressure X Vacuum <br />❑ Hydrostatic <br />❑ Other (Specify) <br />Test Equipment Used: Mechanical Gauge <br />Equipment Resolution: -- <br />ISIMMEM <br />so= <br />Tank # 3 (Diesel) <br />Tank # <br />Tank # <br />Tank # <br />Is Tank Exempt From Testing?' <br />'76 <br />❑ Yes X No <br />❑ Yes ❑ No <br />❑ Yes ONo <br />❑ Yes ❑ No <br />Tank Capacity: <br />101 <br />101 <br />Tank Material: <br />Fiberglass / Steel <br />Tank Manufacturer: <br />Fiber / Steel <br />Product Stored: <br />Diesel <br />Wait time between applying <br />pressure/vacuum/water and <br />I min. <br />starting test: <br />Test Start Time: <br />2:30p.m <br />Initial Reading (RI): <br />-10 hg <br />Test End Time: <br />3:30p.m <br />Final Reading (RF): <br />-10hg <br />Test Duration: <br />lhr. <br />I <br />Change in Reading (RF -R,): <br />0 <br />Pass/Fail Threshold or Criteria: <br />Test Result: <br />x Pass ❑ Fail <br />❑ Pass ❑ Fail <br />❑ Pass ❑ Fail <br />❑ Pass ❑ Fail <br />Was sensor removed for testing? <br />x Yes ❑ No ❑ NA <br />OYes ONo ONA <br />❑ Yes ❑ No ❑ NA <br />❑ Yes ❑ No ❑ NA <br />Was sensor properly replaced and <br />verified functional after testina? <br />x Yes ❑ No ❑ NA <br />❑ Yes ❑ No ❑ NA <br />❑ Yes ❑ No ❑ NA <br />❑ Yes ❑ No ❑ NA <br />Comments — (include information on repairs made prior to testing, and recommended follow-up for failed tests) <br />Secondary containment systems where the continuous monitoring automatically monitors both the primary and secondary <br />containment, such as systems that are hydrostatically monitored or under constant vacuum, are exempt from periodic containment <br />testing. (California Code of Regulations, Title 23, Section 2637(a)(6)) <br />