Laserfiche WebLink
. . . <br /> Scope <br /> This procedurevi||pnovdnaVoador-Qoot/TGoedifiedbechnicianaprocedunatumafolytnst tank overfill <br /> protection. <br /> Reference Documents <br /> • VeaderRoodTLS'8XNOperators Manual (57GOi8-810) <br /> ° VoederRocdTLS'3XX Setup Manual (57GQ13'G28) <br /> ° VeederRootTLS-45DSetup and Operation Screens Manual (577O13'Q4O) <br /> ° VmaderRmotTLG-45QPLUS/TLS4Operator's Manual (577O14'11O) <br /> ° VeederRontTLS4Quick Start(577O14'034) <br /> ° Vued*pRbotCverfi||Alarm Installation Guide(570O18'58Q) <br /> Consoles <br /> TL8'45OPLU8.TL84o,TLS4i.TLS'45Oand TLS3X% <br /> Requirements <br /> TLS-450PLUS,TLS4c,TLS4i,TLS-450:Automatic Event:Device Task programmed to trigger on Tank Overfill and <br /> close orelay feeding voltage tothe Overfill alarm device. <br /> TLS-3XX:Output relay programmed to close a relay on a Tank Overfill alarm feeding voltage to the Overfill alarm <br /> device. <br /> Testing Procedure <br /> 1. Inspection <br /> a. Verify the levels in the tank to make sure there is product in the tank and that the tank is enabled. <br /> b. If the site is currently receiving a delivery,wait until the delivery is complete. <br /> u. Kthe tank isperforming aSLD tank test,stop the test. <br /> 2. Preparation <br /> o. Turn Alarm filtering of as this will allow you toclear alarms quicker. Refer toTLS'3XXSetup manual <br /> (5?8O13-823)orTLS4XXon-line help. <br /> b. Program Delivery delay to 1 minute,this will allow the delivery to be completed quicker. <br /> 1. Note the customers original value,ooyou can restore bafter the test. <br /> 24 <br />