Laserfiche WebLink
• 1 <br /> FtE@E:1\/ED <br /> fr <br /> SWRCB,January 2002 AUG 2 2 201B Page of <br /> 4. TANK ANNULAR TESTING EbUIROMMENTAL <br /> Test Method Developed By: X Tank Manufacturer El Industry Stands ¢1I-TH ssional Engineer <br /> Other(Spec) <br /> Test Method Used: ❑Pressure X Vacuum ❑Hydrostatic <br /> Other(Spec) <br /> Test Equipment Used: Gast Vacuum Pump/Vacuum Gauges in Hg. Equipment Resolution: - '/2"x-30"Hg. <br /> Tank# 1&2 Tank#3 Tank# Tank# <br /> Is Tank Exempt From Testing? No No <br /> Tank Capacity: 20K Split 12/8 6K <br /> Tank Material: Plas/Steel Plas/Steel <br /> Tank Manufacturer: K Steel K&T Steel <br /> Product Stored: Regular 87/Super 91 Diesel <br /> Wait time between applying 10 Minutes 10 Minutes <br /> vacuum and starting test: <br /> Test Start Time: 8:40 8:50 <br /> Initial Reading(Ri): -10"Hg. -10"Hg. <br /> Test End Time: 9:40 9:50 <br /> Final Reading(RF): -10"Hg. -10"Hg. <br /> Test Duration: 1 Hour 1 Hour <br /> Change in Reading(RF-RI): 0"Hg. 0"Hg. <br /> Pass/Fail Threshold or Criteria: No Loss in Hg. No Loss in Hg. <br /> Test Result: Pass Pass <br /> Was sensor removed for testing? Yes Yes <br /> Was sensor properly replaced and Yes Yes <br /> verified functional after testin ? <br /> Comments—(include information on repairs made prior to testing, and recommended follow-up for failed tests) <br /> ' Secondary containment systems where the continuous monitoring automatically monitors both the primary and secondary <br /> containment,such as systems that are hydrostatically monitored or under constant vacuum,are exempt from periodic containment <br /> testing. {California Code of Regulations,Title 23,Section 2637(a)(6)} <br />