Laserfiche WebLink
Spill Bucket Testing Report <br /> 1. FACILITY INFORMATION <br /> Facility Name: Pershing Holdings Inc. Date of Testing: 02/19/2020 <br /> Facility Address: 1329 Escalon Ave. Escalon,CA 95320 <br /> Facility Contact: Sunny I Phone: (209)992-1255 <br /> 2. TESTING CONTRACTOR INFORMATION <br /> Company Name: Diamond Petroleum Services,Inc. <br /> Technician Conducting Test: Guadalupe Sanchez— <br /> Contractor License# 1005444 ICC Certification#5250451 <br /> 3. SPILL BUCKET TESTING INFORMATION <br /> Test Method Used: Hydrostatic <br /> Test Equipment Used: Standard Tape Measure Equipment Resolution: 1/16" <br /> Identify Spill Bucket(By Tank T1: 87 South Fill T1: 87 North Fill T2:91 Fill <br /> Number,Stored Product, etc. <br /> Bucket Installation Type: Direct Bury Direct Bury Direct Bury Direct Bury <br /> x Contained in Sump x Contained in Sump x Contained in Sump Contained in Sum <br /> Bucket Inside Diameter:' 11" 11" 11" <br /> Bucket Depth: 14 '/4" 14" 143/4 <br /> Wait time between•applying 5 minutes 5 minutes 5 minutes <br /> vacuum/water and start of test: <br /> Test Start Time(Ti): 11:11 a.m. 11:11 a.m. 11:12 am. <br /> Initial Reading(Rl): 11 '/." 11 '/." 11 '/," <br /> Test End Time(TF): 12:11 p.m. 12:11 p.m. 12:12 p.m. <br /> Final Reading(RF): 11 '/," 11 '/." 11 '/." <br /> Test Duration(TF—Ti): 1 hr 1 hr l hr <br /> Change in Reading(RF-Rj): 0 0 0 <br /> Pass/Fail Threshold or 1/8" 1/8" 1/8" <br /> Criteria: <br /> Test Result: x Pass Fail x Pass Fail x Pass Fail Pass 0 Fail <br /> Comments: <br /> Technician's Date: 02/19/2020 <br />