Laserfiche WebLink
UNDERGROUND STORAGE TANK <br /> OVERFILL PREVENTION EQUIPMENT INSPECTION REPORT FORM ( Page 71nspection <br /> Type of Action ❑ Installation Inspection ❑ Repair Inspection ® 36 MoI . - FACILITY INFORMATIONCERS IDDate of Overfill Preven <br /> 10181511 4/ 11 / 19 <br /> Business Name (Same as Facility Name or DBA-Doing Business As) <br /> H & M Market ___ - - ---- — <br /> Business Site Address City T95320 <br /> P Code <br /> 2501 Jackson Ave . Escalon <br /> Ila UNDERGROUND STORAGE TANK SERVICE TECHNICIAN INFORMATION <br /> Name of UST Service Technician Performing the Inspection (Print as shown on the ICC Certification.) Phone # <br /> Steven White (408) 971 -2445 <br /> Contractor / Tank Tester License # ICC Certification # ICC Certification Expiration Date <br /> 485184 8898679 6/30/22 <br /> Overfill Prevention Equipment Inspection Training and Certifications (List applicable certifications.) <br /> F . F . # 1016243710 <br /> OPW # 0179368 <br /> III * OVERFILL PREVENTION EQUIPMENT INSPECTION INFORMATION <br /> Inspection Method ® Manufacturer Guidelines (Specify) : OPW 71 SO IOM <br /> Used : <br /> ❑ Industry Code or Engineering Standard (Specify) : <br /> ❑ Engineered Method (Specify): <br /> Attach the inspection procedures and all documentation required to determine the results. <br /> eNo <br /> ed Pages <br /> TANK ID : (By tank number, stored product, etc.) 1 - Regular 2 - Premium 3 - Diesel <br /> What is the tank inside diameter? (Inches) 96" 96" 96" <br /> Is the fill piping secondarily contained? ❑ Yes D No ❑ Yes ® No ❑ Yes ❑ Yes ❑ No <br /> Is the vent piping secondarily contained ? ❑ Yes © No ❑ Yes J❑ No ❑ Yes ❑ Yes ❑ No <br /> Overfill Prevention Equipment Manufacturer(s) OPW OPW <br /> 71 SO 71 SO <br /> What is the overfill prevention equipment response ® Shuts Off Flow ® Shuts Off Flow ® Shuts Off Flow ❑ Shuts Off Flow <br /> when activated? <br /> (Check all that apply.) C1 Restricts Flow El Restricts Flow ❑ Restricts Flow ❑ Restricts Flow <br /> ❑ A/V Alarm ❑ AIV Alarm ❑ AIV Alarm ❑ AN Alarm <br /> Are flow restrictors installed on vent piping? ElYes ❑✓ No [:1Yes ® No ElYes ® No 171Yes ❑ No <br /> At what level in the tank is the overfill prevention set 90 25" 87 . 36" <br /> to activate? (inches from bottom of tank.) - <br /> What is the percent capacity of the tank at which the 91 2% <br /> 0 <br /> overfill prevention equipment activates? 94 . 4 /o - <br /> Is the overfill prevention in proper operating condition ® Yes ❑ Yes ® Yes ❑ Yes <br /> to respond when the substance reaches the <br /> appropriate level? ❑ No (Specify in V.) ® No (Specify in V.) [INo (Specify in V.) ElNo (Specify in V.) <br /> IV. SUMMARY OF INSPECTION RESULTS <br /> Overfill Prevention Inspection Results ® Pass ❑ Fail ❑ Pass ® Fail ® Pass ❑ Fail ❑ Pass ❑ Fail <br /> V. COMMENTS <br /> Any items marked "Fail" must be explained in this section . Any additional comments may also be provided here . <br /> 91 Unable to Extract. Will need bucket Replaced . <br /> VI . CERTIFICATION BY UST SERVICE TECHNICIAN CONDUCTING THIS INSPECTION <br /> I hereby certify that the overfill prevention equipmentwas inspected in accordance with California Code of Regulations , Title 23 , <br /> Division 3, Chapter 16 , Section 2637 . 2 and all the information contained herein is accurate. <br /> UST Service Technician Signature <br /> If the facility has more components than this form accommodates, additional copies of this page may be attached. <br /> CERS = California Environmental Reporting System, ID = Identification, UST = Underground Storage Tank, ICC = International Code Council, AN = Audible and Visual <br /> i <br /> i <br /> i <br />