Laserfiche WebLink
LINE & LEAK DETECTOR TEST REPORT <br /> SITE: JOE'S TRAVEL PLAZA <br /> Identify Time Log of Test Procedures VOLUME REMARKS <br /> Each Line (Military) Ambient Temperature psi READING NET <br /> Weather, Etc. BEFORE AFTER BEFORE AFTER CHANGE Conclusions,Repairs,Comments <br /> DIESEL 1400 PRE TEST 60 <br /> DISP 1415 BEGIN TEST 60 <br /> 16-23 1430 52 50 .0330 .0340 .0010 <br /> 1445 52 50 .0340 .0350 .0010 .0020 <br /> 1450 BLEED BACK 50 0 .0330 .0940 .0610 <br /> DIESEL 1400 PRE TEST 60 <br /> DISP 1415 BEGIN TEST 50 <br /> 22-27 1430 50 50 .0340 .0340 .0000 <br /> 1445 50 50 .0350 .0350 .0000 .0000 <br /> 1450 BLEED BACK 50 0 .0100 .0910 .0810 <br /> MA <br /> ONME <br /> PARTMENT H <br /> Page 2 of 2 <br />