GENERAL MECHANICAL NOTES MECHANICAL LEGEND REVMON$ <br /> 1. EQUIPMENT:ALL EQUIPMENT AND MATERAS SHALL BE NEW AND EQUAL IN QUALITY,TYPE,CAPACITY,EFFICIENCY,AND ACCESSORIES TO THE SYMBOL DESCRIPTION SYMBOL DESCRIPTION <br /> EQUIPMENT INDEED ON THE DRAIMNCS.ADJUSTMENTS TO CONSTRUCTION AND ACCESSORIES ON SUBSTITUTED EQUIPMENT MAY BE REQUIRED N <br /> ACHEVE THIS EQUALITY,AND SHALL BE INCLUDED AT NO FKTRA COST TO THE OWNER.MAKE ANY CHANGES IN DUCTWORK,PIPING,FRAMING, R DUCT RISE L1/C UNDERCUT DOOR <br /> ETC„AS BLOOMED TO ACCOMMODATE SUBSTITUTED EDUIPMENT. IT _ DUCT DROP <br /> 2. INSTALLATION:INSTALL ALL EQUIPMENT AND MATERIALS AND PERFORM ALL WORK IN ACCORDANCE WITH ECNION APPLICABLE CODES INCLUDING DOOR LOWER <br /> BUT NOT LIMITED T0: OSA OUTSIDE AIR -F- <br /> 2013 CALIFORNIA MECHANICAL CODE(ONO) SA SUPPLY AIR SA OUTSIDE AIR <br /> 2013 CALIFORNIA ENERGY CODE(CEC)INCLUDING LOCAL AMENDMENTS RA RETURN AIR 0 puME7Eq DR PHASE <br /> .1 c <br /> G4JFORNA CODE OF RfDULATI0N5{CCR) i�-B) BALANCE DAMPER ABG ABOVE CEILING <br /> 1NAL FIRE PROTECTION ASSOCIATION(NEPA) <br /> 2013 CALIFORNIA FIRE CODE(CFC) 12x10 DUCT(W.H) AE AIR EXTRACTOR <br /> WHERE HDIMfR GAGES OF MATERIAL,LARGER SIZES OR MORE STRINGENT REQUIREMENTS THAN THE CODES ANE REWIRED EY THE CONTRACT <br /> pOCJMENTS,SUCH IN, <br /> RECUIREMENIS SHALL APPLY, - IbIOL ACOUSTICAL LINED DUCTING AP ACCESS PANEL <br /> CFM CUBIC FEET OF ARFlLOw <br /> 3. SHEETMEES WITH <br /> THE <br /> ALL$HINGENTAL DUCTWORK S,AL BE FABRICATED AND INSTALLED!N ACCORDANCE OI CMC ALL BE <br /> RSE AND SMACFLA DUCT 7RANSIHON PER mFEETUIE o <br /> SILVERGUIUIFLNES WITH THE MORE STRINGENT BEING APPLIED.ALL DUCT JOINTS INCLUDING MECHANICAL FLANGED JOINTS SHALL NV SEALED WITH ® ® SUPPLY,RETURN,EXHAUST RISER CLO CEILING N <br /> SILVER TAPE OR ARABOL AND CANVAS.SFiLL THE JOINTS OF ALL DUCTS EIPp5L0 TO THE WEATHER WITH ARAFJOL AND CANVAS,PROVIDE ALE <br /> BRANCH DUCTS WITH VOLUME DAMPERS WITH LOCKING QUADRANTS LOCATED AT LEAST FIVE FEET(5')FROM THE GRILLE OR DIFFUSER SERVED, ©©©© THERMOSTAT,SENSOR,HOMEASTAT,CO2 (F),EXISTING EXISTING TO BE HELD <br /> WITH LONG RADIUS ELBOWS.CONCEALED DAMPERS SHALL HAVE CABLE OPERATED MECHANISMS TO ALLOW ADJUSTMENTS WITH OUT DISTURBING VERIFIED BY DO <br /> R <br /> THE STBUCTIRE.ALL RECTANGULAR OR ROUND RIGID FIRM SHALL BE OF SMACNA GAGE GALVANIZED STEEL OR ALUMINUM,uNLE55 OTHERWISE ��q�� RELOCATE E%IEND/SHONTEN DUCT 'o <br /> NOTED ON THE DRAWINGS.PRrnrtpE FLAT SEAM CONSTRUCTION FOR ANY DUCTS EXPOSED IN OCCUPIED SPACE.NOTE:AL M, <br /> IS NOT AS REOUIIiED FA TA FROM ABOVE,TO ABOVE d <br /> ACCEPTABLE IN LIEU OF ROUND RIGID DUCTWORK.WHERE ROUND SHEET METAL VUCTWGRK!S USED,DUCT SIZES CAN BE REDUCED BY ONE <br /> E. POINT OF CONNECTION FB,TB FROM BELOW.70 BELOW <br /> SIZPO3 <br /> - <br /> 4. DUCT SUPPORTS:AIN ALL PIPING AND DUCTWORK SHALL BE SUPPORTED IN ACCORDANCE WITH CMC STANDARDS OR SMACNA'1GUIDL � MOTORIZED DAMPER AFT ABOVE FINISHED FLOOR <br /> NES FOR € <br /> SEISMIC RESTROF MECHANICAL SYSILMS,CONTRACTOR SHALL PROVIDE CALCULATIONS FOR SEISMIC SUPPORTS AND RESTRAINTS THAT ARE 0- FIRE DAMPER FIT FINISHED FLOOR <br /> ACCEPTASLE TO THE REVIEWING AU7HORGY. 15 /FT PER FOOT r <br /> ��- FIDE SMOKE DAMPER <br /> 5. FLEXIBLE DUCT:FLEXIBLE DUCTS$HALL BE ATCO 30,GCNFLEX F29,THERMAELEX M-K1.OR APPROVED EQUAL.FLEXIBLE DUCTWORK SHALL NOT FIRE SMOKE DAMPER NINC NOT IN MECHANICAL CONTRACT <br /> BE USFD WHERE EXPOSED DUCTWORK OCCURS.SECURE FLEXIBLE DUCTWORK WITH TWO MECHANICALLY APPLIED PLASTIC S7RAPS AT EACH NTS NOT TO SCALE U <br /> FITTING OR ONE WORM DRIVE STEEL CLAMP. FLEXIBLE DUCTWORK MAY BE USED IN LIEU OF RIGJC WIF PRE-APPROVED By ENGINEER. FC FLEXIBLE CONNECTION <br /> 6. INSULATION; <br /> AIRFLOW(OUTLET ARROW) 090 OPPOSED BLADE DAMPER a ��t ` <br /> U'M7�� EFERENCE � CG <br /> AIRFLOW(INLET ARROW) REF RE N G I N E E R I N G <br /> INTERIOR DUCT:INSULATE ALL RIGID SUPPLY AND RETURN BUM WITH 1-1/2'THICK,3/4 PCP DENSITY OWENS CORNING SOPER OR EQUAL, -------- DUCT DEMO TYR TYPICAL p <br /> FIBERGLASS DUCT WRAP,TYPE 75,WITH FOIL REINFORCED KRAFT VAPOR RETARDER FACING,BUTT JOINT PIECES WITH 2"MINIMUM TAP FLAP r <br /> OVERLAPPING.EXTERIOR DUCT:SEAL ALL METAL JOINTS PER SMACKA k CEL.LINE WITH 2'CERTAINTEED TOUGHGPRD,RIDGED LINER BOARD. <br /> TAPE ALL INSULATED INTERIOR JOINTS. WHEN IN CONODIONED SPACE,DUCTS SMALL HAVE R-4.2 INSULATION. WHEN IN UNCONDITIONED 1650 DvvortunRy m,s„A,4yC 911i.7es.71a1 <br /> SPACE,DUCTS SHALL HAVE R-8.0 INSULATION. O Foal I G 95576 T,1.0dm......mm <br /> EXTERIOR DUCT: INSULATION SHALL BE PROTECTED FROM DAMAGE BY MOISTURE,W AND PHYSICAL ABRASION.INSULATION EXPOSED TO <br /> WEATHER S+ALL BE SUI7AULf FOR OUTDOOR SERVILE.PROTECTED BY ALUMINUM,SHEET METAL,PAINTED CANVAS,OR PLASTIC COVER.CELLULAR EQUIPMENT SCHEDULE <br /> FOAM INSULATION SHALL BE PROTECTED AS ABOVE OR PAINTED WITH A COATING THAT IS WATER RETARDANT AND PROVIDES SHIELDING FROM o <br /> SOLAR RADIATION.THE APPLIES TO REFRIGERANT LINE SETS AS WEIL. DUCTS SHALL HAVE R-&0 INSULATION. <br /> SYMBOL DESCRIPTION 3 y1pFEss,;G <br /> 7. DUCT LINER LINE ALL RIGID SUPPLY AND RETURN DUCT DROPS FOR A MINIMUM OF 10 FROM THE UNIT WITH 1'THICK OWENS CORNING <br /> QUIETER ACOUSTICS OR EQUAL ACOUSTIC DUCT LINER,INSTALL WITH 100%COVERAGE ADHESIVE COMPLYING WITH ASTM C 916.AND FURTHER ,s <br /> APPLY TO BUTIED ENDS.MECHANICAL FASTENERS SHALL BE APPLIED 3'FROM COMERS AND 12"OC BEIWEEN CORNER FASTENERS ALL DUCT COOLING WACITIES ARE BASED AT 95 F.AMB.,BO F.DB.67 F.WB,ENTERING AIR TEMPERATURE."EATING TO <br /> DIMENSIONS ON PLANS ARE ttFPR DIMENSIONS.SEAL BUTT ENDS OF EXPOSED INSULATION IN THE DUCTS WITH MANUFACTURERS RECOMMENDED PACCITIES RE BASED <br /> pVOAT 47 BSugsuriTERS IN PLL COOLINGAND HEATING RCS AND MODELST. SIMILAR IN <br /> ' n <br /> SFAIAfII OR ADHESIVE. No,371518 <br /> DIAGNOSTIC CAPABILITY IS REQUIRED FOR ALL NEW DX EQUIPMENT PER CALIFGRNA TITLE 24 SECTION 1201 D EXP,9/3C/',zD15 <br /> 8. CONTROLS:HEATING AND CCOLING CONTROLS SHALL COMPLY WITH THE LATEST EDITION OF C£C(2013),SUBCHAPTLR J.SECTION 120.2.ALL <br /> CONTROLS AND CONTROL MRING ARE NOT SPECIFICALLY SHOWN BUT ARE REQUIRED FOR A COMPLETE AND WORXABLf SY57EM SHALL BE CU HEAT PUMP,MULTI-ZONE OUTDOOR LINT <br /> SUPPLIED BY THE CONTRACTOR AND INSTALLED AT NO ADDITIONAL CGST TO THE OWNER. I FLUITSU MODEL W.: AOU36RLXFZ OR EQUAL, 75 SEER,8.80 EER.COP 355,9.4 HSPF 'Dq CHq"SGA <br /> CCDJNG cvALITY: 35,200 BTU/H f OF GLL� <br /> 9. TESTING:ALL AIR SYSTEMS SHALL BE BALANCED BY A TRAINED MECHANICAL CONTRACTOR,USING AADC.SMACNA,OR NERO PROCEDURES.AIR HEATING CAPACITY; 36,400 BRUIN a _ <br /> QUANTITIES SHALL BE ADJUSTED TO NOT MORE THAN 10%ABOVE OR O%BELOW THE QUANTITIES SHOWN ON THE DRAWINGS.CONTRACTOR RATED INPUT POWER CLG/HiQ: 3,98 KW/3.66 KW o Signed on 6/191/2016 <br /> SHALL SUBMIT A COMPLETE AIR BALANCE REPORT INDICATING,AS A MINIMUM,THE AIR OEUVFRY FOR EACH DIFFUSER,THE FINAL OPERATING ELECTRICAL SERMiCE: 2JOV/IPH/BOHZ <br /> DATA FOR THE SYSTEMS ANO THE AIR CONDITIONING UNOS. TOTAL MAX.CURRENT; 24.1 AMCA' 25 A <br /> c <br /> 10.SUBMITTALS:SUBMIT FOR APPROVAL COWES OF COMPLETE SUBMITTAL CATA DIV SPECIFIED AND PROPOSED EQUIPMENT AND MATERIALS. RECOMMENDED FUSE SIZE: 30A <br /> UBMITTALS <br /> SHALL INCLUDE EQUIPMENT SIZES,CAPACITY,MOTOR LOCATIONS,PERFORMANCE CURVES AND OTHER PERTINENT DATA,EACH WEIGHT: 149 LBS CLIENT <br /> SUBMITTAL SMALL INCLUDE IDENTIFICATIONTAGS OR SYMBOLS TO MATCH OWLS.PARTIAL SUBMITTALS OR SUBMITTALS WHICH ARE X07 MARKED PROVIDE CONVERSION KIT PART j 70 PAIR WITH TWO INDOOR UNITS, <br /> WITH EQUIPMENT TACE OR PERFORMANCE DATA WILL BE REJECTED,EQUIPMENT THAT IS NOT SUBMITTED R TO BE LEFT)AT THE CONTRACTORS � <br /> OWN RISK REGARDLESS OF BRAND OR MOCEL USFO. AH AH WALL-MOUNTED INDOOR UNIT,R-410A <br /> 11.EQUIPMENT IDENTIFICATION:PROVIDE PERMANENT ENGRAVED PLASTIC NAME PLATED FOR ALL EQUIPMENT INSTALLED,INDICATING THE PLAN IA TB FDJITSU MODEL NO.: ASVIaRLF OR EOLAL 0 <br /> DE <br /> ELECTRICAL SEWUL; 2JDV/LPH/fi0HZ H <br /> SIGNATION OF THE UNIT(AC-1,REF„ETC.)AND ALSO THE BUILDING AREA SERVED(CLASSROOMS 2-4,CONFERENCE ROOM,TFC,).STAMPED RUNNING CURRENT CLG/NTG: 0.32 A/0.32 A <br /> METAL TAPES APPLIED WITH SELF-CONTAINED ADHESIVE WILL NOT BE ACCEPTABLE.GLUE TO THE INSIDE COVER THE COMPRESSOR ACCESS RATED POWER USE CLC/BIG: 41 W/91 W <br /> as PANEL,A COPY OF THE EQUIPMENT NAMEPLATE SUBMITTAL DATA WEIGHT: 31 185 <br /> 12,CONTRACTOR SHALL VERIFY ALL WORK CONDITIONS PRIOR TO OONMLNCINC WORK,INCLUDING.BUT NOT LIMITEO 7D:DIMENSIONS,EQUIPMENT, DIGITAL WIRELESS REMOTE CONTROL FILTERS,4-WAY AUTOMATIC LOWERS,AUTO RESTART/RESET,24 HOUR TIMER <br /> STRUCTURAL ELEMENTS AND M0.7ERW-5 INDICATED AS EXISTING.AS WELL AS THE COORDINATED INSTALLATION Or ALL NEW WORK,MATERIALS, a <br /> EQUIPMENT,ETC.COORDNATE THE LOCATION OF ALL ROOF MOUNTED EQUIPMENT WITH THE STRUCTURAL ENGINEER. FF FLY FAN p <br /> 1 2 MAX AIR FLOW,NO.901PN�6-IJ AUR CURTAIN m <br /> 13.OUTSIDE AIR SFwI HOLD COORDINATE OUTLETS <br /> AND INSTALL PACKAGED ROOFTOP EQUIPMENT TO MAINTAIN A MINIMUM OF 10-0'CLEARANCE FROM DON AZEVEDO <br /> OUTSIDE AIR INTAKE TO ALL EXHAUST DUTLETS AND(VTR)VERT THRU ROOF,TYPICAL ELECTRICAL SERVICE: 12OV/IPH/SOHZ, 1/6 HP MOTOR,2A A <br /> WF7CH1; 32 LBS <br /> 14.SUBMITTAL NOTE:MECHANICAL SYSTEMS DESIGN REFLECT EQUIPMENT SPECIFIED.WHEN EQUIPMENT SUBSTITUTIONS OCCUR AND DUCT DESIGN, CEF CEILING EXHAUST FAN `> CONSTRUCTION INC. <br /> DUCT DROPS,CVS INPUT AND ELECTRICAL SERVICE VARIES FROM THAT SPECIFIED,THEN IT SHALL BE THE RESPONSIBLITY OF THE MECHANICAL e PANASONIC WHST PA EIHNG MODEL NO.: FY-17VQ,5 <br /> CONIRACIDR FOR ALL ADDITIONAL ENGINEERING FEES WHEN SUBSTITUTED EQUIPMENT REFLECT A REVISION OR CHANCE ON OUR DRAWINGS. 1 m 980 F STREET#10 <br /> AIR FLOW: 75 CEN,U.25'W.G.S.P. f <br /> 15.INSTALLATION INSTRUCTIONS FOR ALL LISTED EQUIPMENT SHALL BE MADE AVAILABLE TO THE BUILDING INSPECTOR AT THE TIME OF INSPECTION. ELECTRICAL SERVICE: 12CV/LPH/60HZ,20.7 W.C.17 A(CONTROL MTN LIGHTS) WEST SACRAMENTO,CA 956075 <br /> PROVIDE BACKCRAFT DAMPER,ROOF CAP,SPEED CONTROLLER AT FAN HOUSING (916) 586-1020 <br /> 16.ONLY PERMITTED AND WET SIGNED PLANS SHALL BE USED FOR CONSTRUCTION OR BIDDING. WEIGHT: 11 LBS a LIC. 961472t U <br /> a <br /> a <br /> 0 <br /> `c <br /> E <br /> a <br /> C <br /> O <br /> SAN JOAQUIN COUNTY <br /> ENVIRONMENTAL HEALTH DEPARTMENT pE� <br /> 1868 E. HAZTON AVE. <br /> STOCKTQN CA 95205 <br /> (MI)468-3420 <br /> 0.ApproI <br /> Is4pprove0 with-changes: See Remariks 0mch UR <br /> Disapproved:Slee Re marka DUTCH egos. COFFEE <br /> Remarks I " ' 1. 7y (J� s SBTOCKTLINPACIFICAA95204 <br /> - o ORANANc <br /> MECHANICAL <br /> LEGEND, NOTES <br /> Date ;`gy AND SCHEDULES <br /> Appr)Val extends only to th t which is sho and described <br /> 1-' PgWECT ND. CHECKED BY <br /> ..hereon and does not authorize or approve any omission or F 16233 RP/TG <br /> devietiorl from requirements of state laws orr:local ordinances. P A� DRAWN ErY <br /> -- ❑ 08/17/16 DP/JP <br /> 0 <br /> a <br /> 3 <br /> M1.1 <br /> 0 <br />