Laserfiche WebLink
1 <br />SP001 – Formal External Inspection <br /> <br />Customer Name: King Island Marina Inspection Date: 11/5/2020 & 11/24/2020 <br />Contact: Bagley Enterprises / Charles Spurlock (site owner) <br />Site Address: 11530 W. Eight Mile Road. Stockton, CA <br />Phone #: 209-470-8187 <br />Tank ID (if any): <br />Tank Contents: Regular and Premium Gasoline <br />Gross Capacity: 10,000 gallons (4,000 & 6,000 gallon split tank) <br />Year Installed: 1999 <br />Tank mfg: Joor MFG. <br />Tank Model: UL 2085 Fireguard Lightweight Tank <br /> <br />Tank Inspector: Jon Lorente - STI ID: AST-2069 <br /> <br />Review Prior Formal and Periodic Inspections: No Date:_____. Internal / External <br />Copy of prior inspections available for review? No <br />Repair alteration date? No <br />Records of Functionality Testing of Alarms and Equipment ? No <br />Prior Annual Inspections Available for Review: No <br />Prior Monthly Inspections Available for Review: Yes / Adequate: No <br />Operating Inspection Frequency: Annually Monthly Weekly Daily <br />Leak Test or other Inspection Data Available for Review? No If Yes, Date: <br /> <br />Nameplate Date Available / Recorded: No (Contact STI with tank serial # to confirm UL spec.). <br />Industry Standard (Fabrication & Nameplate Data) <br />UL 142 UL 2085 UL 2080 API 650 API 12F Other Not det. Unknown <br /> <br />Tank Dimensions: <br />Rectangular Tank: L:_______. W:_________. H:_____________ <br />Cylindrical Tanks: L:__28’ 6”________. Diameter:___7’11”________. Horizontal / Vertical? <br />Tank Shell Thickness: _1/4” tank shell / 5/16” Bulkheads_______________ <br />Determination Method: Tank Documentation / placards / labels / tank manufacturer / UL Standard) / UTT. <br /> <br />Tank contents confirmed with tank standard : Yes <br />AST observed to be a repurposed UST: No <br />Is Tank inside Building or Covered: No <br /> <br />Overall Tank System Condition: Good Fair Poor Adequate? Yes No (if No, explain): Repair coating failures. <br /> <br />Primary Tank Material: Steel Fiberglass Other Thickness: Basis: UT Spec <br />Secondary Containment Material: Steel Fiberglass Concrete None <br /> <br />Tank Corrosion Protection: Paint/Epoxy Coating Cath.Prot. Other Coating None Adequate? Yes No <br /> <br />Coating Failure on Secondary Tank Shell: *Yes No (If Yes, Consider UTT). <br />*Double-wall AST’s do not require UTT readings for the primary tank. If Corrosion is evident on the outside <br />surface of the secondary tank, UTT readings are required. <br /> <br />Tank Heads: Good Fair Poor - Coating Failure? NO Adequate? Yes <br />Tank Shell: Good Fair Poor - Coating Failure? Yes Adequate? No <br />Tank Chime: Good Fair Poor – N/A <br />Cathodic Protection System: N/A