SAN JOAQUIN <br />CCUNT <br />Environmental Health Department <br />Underground Storage Tank Program Inspection Report <br />Facility Name: <br />Facility Address: <br />Date: <br />Tracy Texaco <br />2375 N TRACY BLVD, TRACY <br />September 08, 2020 <br />SUMMARY OF VIOLATIONS <br />(CLASS I, CLASS II, or MINOR - Notice to Comply) <br />Item # <br />Remarks <br />209 <br />CCR 2716(a -e) Failure to conduct the designated UST operator visual inspection at least once every 30 days. <br />1) OBSERVATION: Designated operator reports were not signed within the required time frame. <br />-The 11/7/2019 designated operator report was signed by the owner/operator on 11/17/2019. <br />-The 12/6/2019 designated operator report was signed by the owner/operator on 12/16/2019. <br />REGULATORY GUIDANCE: Within 48 hours of the completion of the designated UST operator visual inspection, <br />the designated operator shall sign and provide the owner or operator with a copy of the inspection report. Within 48 <br />hours of being provided a signed copy of the report, the owner or operator shall provide a description of each <br />corrective action taken or to be taken and shall sign and date the report, acknowledging the identified compliance <br />issues. <br />CORRECTIVE ACTION: Ensure all designated operator inspection reports are completed and signed within the <br />required time frame in the future. <br />2) OBSERVATION: The designated operator failed to document all the alarms from the attached alarm history on <br />the designated operator inspection report and failed to check that they were responded to appropriately. The <br />missing alarms include: L4 sensor out alarm on the 91 annular space (8/18/2020 and 8/16/2020) <br />REGULATION GUIDANCE: During the inspection, the designated operator shall review the alarm history since the <br />previous inspection, check that each alarm was documented and responded to appropriately, and attach a copy of <br />the alarm history with documentation taken in response to any alarms to the inspection report. <br />CORRECTIVE ACTION: Ensure that designated operators performing inspections at this facility are including all of <br />the required information on the reports. <br />3) OBSERVATION: The designated operator failed to check and note all required items on the visual inspection <br />reports. The incorrect and missing information included the following from the inspection reports: <br />-Tank and line tightness test information was left blank. <br />-Secondary containment test information was left blank. <br />-The designated operator answered the question regarding sump sensor locations but did not list which sumps were <br />visually inspected. <br />-The designated operator documented visual inspections of sumps, but left the question regarding sump sensor <br />locations blank. <br />-The designated operator documented visual inspections of UDCS, but left the question regarding sump sensor <br />locations blank. <br />-The "N/NA" in sections VII through XI were not fully explained in section III of the report. <br />REGULATION GUIDANCE: During the visual inspection, the designated operator shall check that all required <br />testing and maintenance for the UST system have been completed and shall check all required items on the report. <br />CORRECTIVE ACTION: Ensure that designated operators performing visual inspections at this facility are including <br />all of the required information on the reports. <br />4) OBSERVATION: The designated operator failed to check and note the correct test dates for overfill prevention <br />FA0006443 PR0231897 SCO01 09/08/2020 <br />EHD 23-01 Rev. 9/20/2019 Page 7 of 8 Underground Storage Tank Program OIR <br />1868 E. Hazelton Avenue I Stockton, California 95205 1 T 209 468-3420 1 F 209 464-0138 1 www.sjcehd.com <br />