Laserfiche WebLink
and both AST and the berm are suitable for continued usage. Leak detection is visually ascertained via <br /> visual inspection of secondary containment area. Berm containment capacity is approximately 450 gals. <br /> 16. Damage to AST or systems. No damage reported by Owner/Operator. Upon inspection,no evidence of <br /> weld breaks punctures cracks or other structural damage to the berm. Upon inspection,there was no <br /> evidence of cracks, breaks, punctures or other structural damage to the primary vessel. Leak detection is <br /> assured via inspections of the secondary containment. Poly thickness measured to 7.8 mm. average. Steel <br /> thickness of the berm was measured to .110 in. thickness,which would be in excess of steel thickness <br /> minimums under UL 142. <br /> 17.Comments Tank has a 1 '/4 in. closed fitting at base of tank. Tank had approximately 155 gals.of product <br /> at the time of the inspection. <br /> a. Dimensions of AST: Primary Vessel= 300 gallons capacity total <br /> Dimensions: Primary Tank: 38 in.Diam X 67 in. L./ lin. crown top ( 16 in. opening for product <br /> removal. <br /> Secondary Berm: 60 in.W X 73 in. L X 24 in.Ht <br /> b. Product stored: used (waste) oil/Specific Gravity=.950 <br /> c ( 1 ) 4 in atmospheric vent on primaiycontainment( 0 ) in. emergency vent on primary vessel <br /> d ( 0 ) in atmospheric vent on secondary containment( 0 ) in. emergency vent on secondary vessel <br /> PE certification <br /> 1 certify under penalty of law that this document and all attachments were prepared under my direction or supervision in <br /> accordance with a system designed to assure that qualified personnel properly gather and evaluate the information submitted. <br /> Based on my inquiry of the person or persons who manage the system, or those persons directly responsible for gathering the <br /> information, the information submitted is, to be the best of my knowledge and belief, true, accurate, and complete. I am aware <br /> that there are significant penalties for submitting false'formation, including the possibility of fine and imprisonment for <br /> knowing violations. I/'/ <br /> I have reviewed the data and confirm it complies /does not complywith CCR section 66265.192(k) <br /> QVESS/QN9� �o6�Rr �iy/lllTE�.��i1/ <br /> e PrinteName of egi red PE <br /> .63087 z ignature of egistered PE <br /> E% 06-3 20 <br /> (seal)Date �,2/L�/�� Registration Number 00Y State <br />