Laserfiche WebLink
The following is an itemized list of aboveground petroleum storage act violations that <br /> have not been addressed for ACAMPO AG SVC as of June19, 2020. <br /> Open violations from July 24, 2018 inspection <br /> Violation #710 -Plan failed to adequately discuss procedures to test or inspect each container for integrity. <br /> The SPCC plan did not discuss an industry standard that will be used for inspections and testing of the tanks. The <br /> frequency and industry standard for formal inspections was not discussed in the plan and the qualifications of the <br /> person conducting the formal tests and inspections were not discussed. Each aboveground container shall be <br /> tested and inspected for integrity on a regular schedule and whenever repairs are made. The qualifications of <br /> personnel performing tests and inspections, frequency and type of testing and inspections that take into account <br /> container size, configuration, and design shall be determined in accordance with industry standards. Examples of <br /> these integrity tests include, but are not limited to: visual inspection, hydrostatic testing, radiographic testing, <br /> ultrasonic testing, acoustic emissions testing, or other systems of non-destructive testing. <br /> ❑ This violation was corrected ❑ This violation will be corrected by (date): <br /> ❑ Supporting documents included <br /> Describe actions taken or will be taken to correct violation: <br /> Page 1 of 1 <br />