Laserfiche WebLink
xAft <br /> INDIVIDUAL TANK INFORMATION AND TEST RESULTS <br /> ®Tanknology <br /> 8501 N MOPAC EXPRESSWAY,SUITE 400 <br /> TEST DATE: 05/27/11 AUSTIN,TEXAS 78759(512)451-6334 WORK ORDER NUMBER: 2281427 <br /> CLIENT: COSTCO WHOLESALE SITE: COSTCO LODI <br /> I ii 10 <br /> 10 110 1 1 <br /> Tank ID: 87-A 1 Tank manifolded: No Bottom to top fill in inches: 179.0 <br /> Product: REG UNLEAD Vent manifolded: YES Bottom to grade in inches: 19.9 <br /> Capacity in gallons: 29,816 Vapor recovery manifolded: YES Fill pipe length in inches: 60.0 <br /> Diameter in inches: 119.00 Overfill protection: YES Fill pipe diameter in inches: <br /> Length in inches: 629 Overspill protection: YES Stage I vapor recovery: DUAL <br /> Material: DW FIBERG Installed: ATG Stage II vapor recovery: ASSIST <br /> CP installed on: <br /> COMMENTS <br /> Provides product for disp 1/2,5/6,9/10,13/14 <br /> vac sensors in stp sumps requires second man to be able to test sensors as you need to get into sump <br /> to test these sensors. <br /> PSI at tank bottom: New/passed Failed/replaced New/passed Failed/replaced <br /> Fluid level in inches: L.D.#1 L.D.#1 L.D.#2 L.D.#2 <br /> UFT/OFT: Make: vEEDERROOT <br /> Fluid volume in gallons: Model: ELECTRONIC <br /> Tank water level in inches: S/N: 310983 <br /> Test time: NOT Open time in sec: <br /> Number of thermisters: TESTED Holding psi: 22 NOT <br /> Specific gravity: Resiliency cc: TESTED <br /> Water table depth in inches: Test leak rate ml/m: 189.0 <br /> Determined by(method): Metering psi: <br /> Leak rate in gph: Calib.leak in gph: 3.00 <br /> Result: Results: PASS <br /> COMMENTS COMMENTS <br /> Test time: <br /> Ullage volume: Material: DW FIBERG <br /> Ullage pressure: Diameter(in): 2.0 <br /> Results: Length(ft): 150.0 <br /> Test psi: <br /> DATA FOR LITS-4T ONLY: Bleedback cc: <br /> Time of test 1: Test time(min): <br /> Temperature: NOT Start time: NOT NOT NOT NOT <br /> Flow rate(cfh): TESTED End time: TESTED TESTED TESTED TESTED <br /> Time of test 2: Final gph: <br /> Temperature: Result: <br /> Flow rate(cfh): Pump type: PRESSURE <br /> Time of test 3: Pump make: FE PETRO <br /> Temperature: <br /> Flow rate(cfh): Impact Valves Operational: YES <br /> COMMENTS COMMENTS <br /> LI I I <br /> Printed 06/08/201107:23 MTUTTLE <br />