INVOICE #JB000401 ; TW$, 2-DME: 06/14/99 <br /> AFFORDA-TEST <br /> PO BOX 36 <br /> THORNTON, CA. 95686 <br /> 209 794-0102 FAX 209 794-0112 <br /> TANK STATUS EVALUATION REPORT <br /> ----------------------------- <br /> ***** CUSTOMER DATA ***** ***** SITE DATA ***** <br /> RADIAN INTERNATIONAL DSS CONSTRUCTION ENGINEERS <br /> 11297 COLOMA RD. 655 W. CLAY <br /> RANCHO CORDOVA, CA. STOCKTON, CA. <br /> 95670 <br /> CONTACT: HOVERMAN, KEVIN <br /> PHONE #: <br /> ***** COMMENT LINES ***** <br /> 20K DIESEL - 6K RUL - DIESEL DOUBLE SUCTION PUMP & A BULK <br /> LOADER PRESSURE LINE - PRESSURE RUL LINE - BALANCED VR <br /> VEEDER-ROOT TLS-350 <br /> CURRENT EPA STANDARDS DICTATE THAT FOR UNDERGROUND <br /> FUEL TANKS, THE MAXIMUM ALLOWABLE LEAK/GAIN RATE OVER THE PERIOD <br /> OF ONE HOUR IS .05 GALLONS. ULLAGE TEST IS PASS/FAIL ONLY. <br /> TANK #1: DIESEL FUEL 2 TYPE: E-GLASS RATE: .006760 G.P.H. GAIN <br /> ULLAGE: PASS SIGNAL/NOISE: -.07 <br /> TANK IS TIGHT. <br /> TANK #2: REG UNLEADED TYPE: E-GLASS RATE: .005294 G.P.H. GAIN <br /> ULLAGE: PASS SIGNAL/NOISE: -.03 <br /> TANK IS TIGHT. <br /> EQUIPMENT: USTEST <br /> OTTL# 97-1143 <br /> OPERATOR: LYLE D. NIMMO SIGNATURE: �-'� � <br />