Laserfiche WebLink
AFFORDA-TEST 209 794 0112 F. 02 <br /> INVOICE #J8000401 TEST DATE: 06/14/99 <br /> AORDA-TEST <br /> PO BOX 36 <br /> TO TON, CA. 95656 <br /> 209 794-0302 FAX 209 794-0112 <br /> TANK STATUS EVALUATION REPORT <br /> ----------------------------- <br /> * * CUSTOMER DATA **** ***** SITE DATA **** <br /> RADIAN INTERNATIONAL DSS CONSTRUCTION ENGINEERS <br /> 21297 COLOMA RD. 655 W. CLAY <br /> RANCHO CO DOVA, C . STOCKTON, CA. <br /> 95670 <br /> CONTACT: HOVE , KEVIN <br /> PHONE #: <br /> ***** COMMENT LINES *** <br /> 20K DIESEL - 6K RUL - DIESEL DOUBLE SUCTION PUMP BULK <br /> LOADER PRESSURE LINE - PRESSURE RUL LINE - BALANCED VR <br /> V - TLS-350 <br /> CURRENT EPA STANDARDS DICTATE THAT FOR UNDERGROUND <br /> FUEL TANKS, THE MAXIMUM ALLOWABLE LEAK/GAIN RATE OVER THE PERIOD <br /> OF ONE HOUR IS .05 GALLONS. ULLAGE TEST IS PASS/FAIL ONLY. <br /> TANK #1: DIESEL FUEL 2 TYPE: E-GLASSRATE: .006760 G.P.H. GAIN <br /> UL E: PASS SIGN /NOISE: -. 7 <br /> TANK IS TIGHT. <br /> TANK 12: REG UNLEADED TYPE: EPG TE: .005294 G.P.H. GAIN <br /> UL G : PASS SIGN /NOISE: -.03 <br /> TANK 19 TIGHT, <br /> EQUIPMENT: USTEST <br /> OTTL# 97-1243 l <br /> OPERATOR: LYLE D. N114MO SIGNATURE: t <br />