Laserfiche WebLink
GENERAL CONSTRUCTION <br />SERVICE STATIONS <br />BULK PETROLEUM PLANTS <br />PETRO -TITS TANK TESTING <br />03/09/90 <br />W <br />TRIfNGLE INC., OF SACRA"NTO <br />P.O. BOX 9795 SACRAMENTO, CALIFORNIA 95823 3526 62nd AVENUE <br />State License No. 183550 <br />Phone (916) 421-I990 Fax 916-421-0642 <br />APPLICATION FOR PERMIT TO REMOVE UNDERGROUND FUEL TAMKS <br />ITEM #6 - Decontamination Procedure <br />Pump out remaining product.' <br />Triple rinse tank with water and remove with vacuum truck <br />as hazardous waste by California Oil Recyclers Inc., hauled <br />and disposed of by them. <br />ITEM #7 - Purge Tank <br />Purging of tank to be done by putting 15 lbs. of dry ice <br />in tank for each 1,000 gallons of tank volume two (2) <br />hours prior to removal, plug all openings with one plug <br />having 1/4" hole for expansion. <br />ITEM #8 - Soil Sample - Obtain per following <br />After tank has been removed from excavation, back hoe bucket ' <br />is cleaned and takes a scoop from area under tank as directed by <br />field inspector, grab sample is taken with brass tube by <br />laboratory testing company and back to lab for testing. <br />L. H. Chronis <br />Vice -President <br />a <br />