Laserfiche WebLink
SWRCB, January 2002 <br />1] <br />7. UNDER -DISPENSER CONTAINMENT UDC TESTING <br />Page of <br />Test Method Developed By: ❑ UDC Manufacturer ❑ Industry Standard X Professional Engineer <br />❑ Other (Spec) <br />Test Method Used: ❑ Pressure ❑ Vacuum X Hydrostatic <br />❑ Other (Spec) <br />Test Equipment Used: Caldwell Level Change Indicator Equipment Resolution: .002 <br />UDC # 1 -Diesel UDC # 2 -Gasoline UDC # UDC # <br />UDC Manufacturer: Total Containment Total Containment <br />UDC Material: <br />Poly Plastic Poly Plastic <br />UDC Depth: <br />38" 38" <br />Height from UDC Bottom to Top <br />14" 10" <br />of Highest Piping Penetration: <br />Height from UDC Bottom to <br />21" 20" <br />Lowest Electrical Penetration: <br />Condition of UDC prior to <br />Dry Dry <br />testing: <br />Portion of UDC Tested <br />Water Level 24" Water Level 24" <br />Does turbine shut down when <br />UDC sensor detects liquid (both <br />IXYes No [INA X Yes No ❑ NA <br />product and water)?* <br />Turbine shutdown response time <br />Not Alarmed Not Alarmed <br />Is system programmed for fail- <br />safe shutdown?` <br />X Yes []No ❑ NA X Yes ❑ No ❑ NA <br />Was fail-safe verified to be <br />Yes X No ❑ NA Yes X No ❑ NA <br />o erationalf <br />Wait time between applying <br />5 Minutes 5 Minutes <br />water and starting test <br />Test Start Time: <br />11:35 12:25 <br />Initial Reading (RI): <br />.001 .001 <br />Test End Time: <br />12:05 12:55 <br />Final Reading (RF): <br />.001 .001 <br />Test Duration: <br />1 30 Minutes 30 Minutes <br />Change in Reading RF -RI : <br />0 0 <br />Pass/Fail Threshold or Criteria: <br />.005/30 Minutes .005/30 Minutes <br />Test Result: <br />X Pass 0 Fail X Pass 0 Fail ❑ Pass < 0 Fail <br />0 Pass 0 Fail <br />Was sensor removed for testing? <br />X Yes ❑ No ❑ NA X Yes ❑ No [INA ❑ Yes ❑ No ❑ NA <br />❑ Yes ❑ No [INA <br />Was sensor properly replaced and <br />X Yes ❑ No ❑ NA X Yes ❑ No P. NA ❑ Yes ❑ No ❑ NA <br />❑ Yes ❑ No ❑ NA <br />1 <br />verified functional after testin ? <br />11 <br />Comments — (include information on repairs made prior to testing, and recommended follow-up for failed tests) <br />' If the entire depth of the UDC is not tested, specify how much was tested. If the answer to anv of the questions indicated with an <br />asterisk (*) is "NO" or "NA", the entire UDC must be tested. (See SWRCB LG -160) <br />