Laserfiche WebLink
San Joaquin County <br />Environmental Health Department <br />1868 East Hazelton Avenue, Stockton, California 95205-6232 <br />Telephone: (209) 468-3420 Fax: (209) 468-3433 Web: www.sjgov.org/ehd <br />Underground Storage Tank Program Inspection Report <br />Facility Name: <br />Facility Address: <br />Date: <br />QUICK STOP MART* <br />2057 S EL DORADO ST STOCKTON <br />Aril 21 2015 <br />SUMMARY OF VIOLATIONS <br />(CLASS I, CLASS II, or MINOR - Notice to Comply) <br />Item # <br />Remarks <br />210 <br />CCR 2715(f)(2) Unstaffed facility failed to have or implement a training program approved by the EHD. <br />The designated operator employee training was not performed. For facilities that are not routinely staffed, the <br />designated operator shall implement an employee training program approved by the EHD. Ensure that employees <br />have been trained by the designated operator, maintain the list on site, and submit a copy of the training records to <br />the EHD. <br />This is a Class II violation. <br />301 <br />HSC 25292.1 UST system is not operated to prevent unauthorized release, including spills and overfills. <br />The facility is not currently in operation. The monitoring panel is currently displaying sensor out alarms for all three <br />sensors at the facility (1-1, L2, L3 - the sumps sensors for both STP sumps and the tank annular sensor). According <br />to Mr. Dhillon, the wiring was cut several weeks ago when someone broke into the facility. The monitoring system is <br />down and the tanks are not currently being monitored. The underground storage tank system shall be operated to <br />prevent unauthorized releases. Immediately correct by doing either of the following: <br />- Have a properly licensed, trained, and certified contractor repair or replace the monitoring system in order to restore <br />continuous tank monitoring, with functional components (LG 113-x listed, if applicable), and obtain a permit within one <br />business day from the EHD. <br />- Obtain a permit from the EHD to temporarily close this UST system and perform the closure under inspection by the <br />EHD. <br />This is a repeat violation, Class II. <br />302 <br />HSC 25291(b) UST system incapable of detecting leak from primary into secondary containment (pre -Jul 2003). <br />The annular sensor is not functional and, therefore, the tank is not monitored. The facility is not currently in operation. <br />The monitoring panel is currently displaying sensor out alarms for all three sensors at the facility (1-1, L2, L3 - the <br />sumps sensors for both STP sumps and the tank annular sensor). According to Mr. Dhillon, the wiring was cut <br />several weeks ago when someone broke into the facility. The monitoring system is down and the tanks are not <br />currently being monitored. The interstitial space shall be monitored with a monitoring system connected to an <br />audible and visual alarm system. Immediately correct by doing either of the following: <br />- Have a properly licensed, trained, and certified contractor repair or replace the monitoring system in order to restore <br />continuous tank monitoring, with functional components (LG 113-x listed, if applicable), and obtain a permit within one <br />business day from the EHD. <br />- Obtain a permit from the EHD to temporarily close this UST system and perform the closure under inspection by the <br />EHD. <br />This is a repeat violation, Class II. <br />Received b <br />(initial): <br />Inspector:� <br />STACY RIVERA, Senior REHS v1 <br />Phone: <br />(209) 468-3440 <br />Date: <br />04/21/2015 <br />Page 7 of 10 <br />