Laserfiche WebLink
RECEIVED <br /> MAR 2 7 2017 <br /> ENVIRONMEN SAL HEALTH <br /> PERMIVSEWOES <br /> Quality Petroleum Equipment <br /> LDT - 890 Test Form <br /> Test Information <br /> Date: 2/9/2017 Test Company: Mid Valley Consulting) & General Eng. <br /> Telephone: 530-749-9892 Contact: James Day <br /> Site ID Quick N Easy Mart Address: 2057 S EI Dorado <br /> City: Stockton State: CA, <br /> Type of Test Equipment: VMI LDT-8901AF <br /> Submersible Pump Identification <br /> MFG: FE PETRO Model No: STP150VL2-00 Serial No 0610 <br /> Leak Detector Identification <br /> MFG: VMI Model No: LD 2000 Serial No: 1291 <br /> Replacement Leak Detector Identification <br /> MFG Model No: Serial No <br /> Line Conditions <br /> 1. Type of Pipe: FRP 2. Diameter of Pipe: 3/2 3. Length of Pipe 75' <br /> 4. Burial Depth of Leak Detector: 28" S. Kind of Fuel: 87 6. Date of Last Test: 2016 <br /> Test Conditions <br /> 1. Operating Pump Pressure: 30 2. Gallon per hour test rate:_3_ Q10 psi <br /> 3. Static Line Pressure (Pump Off): 19 4. Bleed back Test (Pump : 135_ l <br /> 5. Step-Through time to full flow 3 seconds (0 psi to full pump pressure, no leak) <br /> 6. Leak detector stays in Leak Search Position with a 3 GPH leak-Yes: X PASS o: FAIL <br /> 7. Was the leak detector adjusted-Yes: No: <br /> Symptoms <br /> 1. Won't find 3 GPH leak: 2. Stays in Slow Flow: <br /> 3. Other: <br />