0 0 <br />R.W. WILLIAMS, INC. <br />P.O. Box 417841 <br />Sacramento, CA 95841-7841 <br />Phone 1-800-826-2729 <br />August 27, 1990 <br />Fillner Construction Co. <br />2180 Enterprise Blvd. <br />West Scramento, CA SS691 <br />Attn: Steve Welge <br />Re: Tank system testinS, August 26, 1990 <br />2320 N. El Dorado, Stockton, CA <br />Dear Sir, <br />-N <br />nk <br />EN -- E6 <br />A <br />UG <br />E N V 1 R C) 'A i TH" <br />The tank sy2tems -tested at this location are identified as <br />follows: <br />Tank system #1 Unleaded <br />Tank --y-stem #2 Super Unleaded <br />The California Water Resources Control Boards criteria for <br />a tight tank system is a systei,,i with a leak rate less than <br />.050 gallons per hour for tank systems 12,000 gallons or <br />j <br />less. These are calculated, mathematical tolerances only and <br />are riot meant to indicate the permission of any leak. <br />During the stand -pipe test procedure the liquid hydrostatic <br />pressure applied to -the underground tank system is generally <br />two to -three times greater than normal liquid storage <br />pressures. This .increase in hydrostatic pressure will <br />amplify the indicated rate of leak accordingly. <br />Tank system #1 showed a ieak rate of -.016 gal./hr. <br />Tarok tegi #1 i <br />Tank system #2 showed a leak rate of -.026 gal./hr. <br />Tank system #2 is tight. <br />Should you have any questions re8uardin8 the results of <br />testing please feel. 'free t.o contact us at anytime. <br />Sincerely, <br />R. W. WLL T AMS, INC. <br />