Laserfiche WebLink
SWRCB, January 2006 <br />Spill Bucket Testing Report Form <br />This form is intended for use by contractors performing annual testing of UST spill containment structures. The completed form and <br />printouts from tests (if applicable), should be provided to the facility owner/operator for submittal to the local regulatory agency. <br />1. FACILITY INFORMATION <br />Facility Name: ELDORADO FOOD SHELL I Date of Testing: 02-08-11 <br />Facility Address: 2320 NORTH ELDORADO BLVD STOCKTON CALIFORNIA95204 <br />Facility Contact: BOB Phone: 209-943-1311 <br />Date Local Agency Was Notified of Testing: <br />Name of Local Agency Inspector (if present during testing): SAN JOAQUIN CO GARRETT <br />2. TESTING CONTRACTOR INFORMATION <br />Company Name: AFFORDA TEST 4162 nd Street Galt, CA 95632 (209) 744-0112 Fax: (209) 744-0116 <br />Technician Conducting Test: ❑ Lyle D. Nimmo ❑ Zane A. Nimmo ❑ David A. Winkler ® Felix G. Ramirez <br />5249115 -UT 5263322 -UT 5263373 -UT 5273934 -UT <br />Credentials': 0 ICC Service Tech. ® SWRCB Tank Tester <br />3. SPILL BUCKET TESTING INFORMATION <br />Test Method Used: ® Hydrostatic ❑ Vacuum Other <br />Test Equipment Used: TAPE H2O Equipment Resolution: 1/16 <br />Identify Spill Bucket (By Tank 1 87 2 91 3 DIE 4 <br />Number, Stored Product, etc) <br />® Direct Bury 0 Direct Bury Direct Bury Direct Bury <br />Bucket Installation Type: ❑ Contained in Sump ❑ Contained in Sump ® Contained in ❑ Contained in <br />Sum Sum <br />Bucket Diameter: 11 11 11 <br />Bucket Depth: 13 13 13 <br />Wait time between applying <br />vacuum/water and start of test: <br />Test Start Time (TO: 930 930 930 <br />Initial Reading (RI): 12 12 111/4 <br />Test End Time (TF): 1030 1030 1030 <br />Final Reading (RF): 1 12 12 111/4 <br />Test Duration (TF — TI): 1 HOUR 1 HOUR 1 HOUR <br />Change in Reading (RF - Rj): 0 0 0 <br />Pass/Fail Threshold or 0 0 0 <br />Criteria: <br />Test Result: 0 Pass ❑; Fail CDPass [] Fail 0 Pass ❑ Fail ❑ Pass ❑ Fait <br />Comments — (include information on repairs made prior to testing, and recommended follow-up for failed tests) <br />CERTIFICATION OF TECHNICIAN RESPONSIBLE FOR CONDUCTING THIS TESTING <br />I hereby certify that all the information contained in this report is true, accurate, and in full compliance with legal requirements. <br />lr� <br />Technician's Signature: Date: <br />' State laws and regulations do not currently require testing to be performed by a qualified contractor. However, local requirements <br />may be more stringent. <br />