Laserfiche WebLink
' USTMAN SIR SYSTEM <br />Monthly Monitoring Report <br />MAY, 1994 <br />Report Date: 06/21/94 <br />Company name :QUIK STOP MARKETS INC. <br />Station Name: QUIK STOP MARKET Station # : 39 <br />Address: 2285 E FREMONT STREET City: STOCKTON State: CA <br />PART A: <br />------------------------------------------------------------------------- <br />Data <br />Tank ID: Tank and Lines Status: Product: Quality: Dels : Sales <br />PUL TIGHT PREMIUM FAIR 6257 4895 <br />RUL TIGHT REGULAR UNLEADED GOOD 46015 47989 <br />USTMAN INDUSTRIES INC. is a certified Statistical Inventory Reconciliation <br />(SIR) release detection vendor. Tank status results for monthly monitoring <br />are based on parameters specified by the EPA protocol for SIR methods. <br />PART B: Comments and Recommendations <br />O/S listed below represent removals, additions or delivery discrepancies <br />which were accounted for as part of the SIR analysis. <br />PUL (5/9/1994:DEL -179) (5/14/1994:DEL 103} (5/22/1994: 160} <br />(5/25/1994:DEL -233} (5/29/1994: -3732) (5/30/1994: 3832) <br />RUL (5/7/1994: -125} (5/8/1994: 2071 (5/19/1994:DEL -133} <br />(5/22/1994: 260} <br />For regulatory compliance in California, a piping integrity test <br />every 12 months and a tank integrity test every 24 months are <br />required in association with SIR monthly monitoring. <br />