LINE LEAK DETECTOR (LLD) TEST REPORT - 102-01-1 <br /> TEST DATE: August 8, 2017 <br /> _. 7 . <br /> Al. FACILITY A2. OWNER <br /> Name Quik Stop Market#39 Name Quik Stop Markets, Inc. <br /> Address 2285 E.Fremont Street,Stockton,CA 95205 Address 4567 Enterprise Street,Fremont,CA 94538 <br /> Phone# 510-657-8500 Phone# 510-657-8500 <br /> Contact Roger BatraContact Debbie Markovich <br /> A3. C U P A A4. TESTING CONTRACTOR <br /> Name San Joaquin County Environmental Health Name Walton Engineering, Inc. <br /> Address 1868 E.Hazelton Avenue,Stockton,CA 95202 Address P.O.Box 1025,W.Sacramento,CA 95691 <br /> Notified July 27,2017 Lic# 617238 A,B,Haz <br /> Inspector Cesar Ruvalcaba Contact Veronica Freitas <br /> Phone# 209-468-3442 Phone# 916-373-1166 <br /> I. LINE LEAK DETECTOR TEST RESULTS <br /> Test Equipment Used: Va orless VMI ADT-890 <br /> Tank number 1 2 <br /> Product contained Gasoline-87 Gasoline-91 <br /> Leak Detector Type MLLD MLLD <br /> Leak detector make/model VMI 99LD-2000 VMI 99LD-2000 <br /> Serial number Illegible 5061506 <br /> Functional Element Holding (psi) 30 29 <br /> Resiliency (ml) 55 55 <br /> Test leak rate (gph) 3.00 3.00 <br /> Pump pressure (psi) 30 29 <br /> Metering pressure (psi) 18 17 <br /> Pressure Restriction Reduction (psi) 12 12 <br /> Length of Restriction Test (seconds) 30 30 <br /> Full Flow Opening time (seconds) 3 5 <br /> TEST RESULT PASS PASS <br /> Tank number <br /> Product contained <br /> Leak Detector Type <br /> Leak detector make/model <br /> Serial number <br /> Functional Element Holding (psi) <br /> Resiliency (ml) <br /> Test leak rate (gph) <br /> Pump pressure (psi) <br /> Metering pressure (psi) <br /> Pressure Restriction Reduction (psi) <br /> Length of Restriction Test (seconds) <br /> Full Flow Opening time (seconds) <br /> TEST RESULT <br /> J. COMMENTS: <br /> � J ALTON <br /> Signature: NWHEERING MC. <br /> Technician: Thomas Steiger A31060/8156310 Date: August 8,2017 <br />