Laserfiche WebLink
9 <br /> Page of <br /> 7.UNDER-DISPENSER CONTAINMENT C TESTING <br /> Test Method Developed By: X UDC Manufacturer ❑Industry Standard ❑Professional Engineer <br /> ❑Other(Spec) <br /> Test Method Uses: ❑Pressure ❑Vacuum X Hydrostatic <br /> ❑Other(Spec) <br /> Measuring Equipment Used for Testing: UST 2000P <br /> UDC#7/8 <br /> UDC Manufacturer: BRAVO <br /> UDC Material: STEEL <br /> UDC Depth: 12" <br /> Height from UDC Bottom to Bottom of Box <br /> Highest Piping Penetration: <br /> Height from UDC Bottom to Bottom of Box <br /> Lowest Electrical Penetration: <br /> Condition of UDC prior to FAIR <br /> testing: <br /> Portion of UDC Tested ENTIRE BOX <br /> Wait time between applying @10 MIN <br /> pressure/vacuum/water and starting <br /> test: <br /> Test Start Time: 1127 <br /> Initial Reading(RI): .8906 <br /> Test End Time: 1133 <br /> Flrial Readin (RF): .8900 <br /> Test Duration: 6IN <br /> Change in Reading(RF-R,): -.0006 <br /> Pass/Fail Threshold: +/-.001 <br /> Test Result: PASS <br /> Was sensor removed for YES <br /> testing? <br /> Was sensor properly replaced YES <br /> after testing? <br /> Comments— (include information on repairs made prior to testing) <br /> Floats removed for testiny- and then replaced <br /> All UDC's Pans 12 x 14 x 40 <br /> 55 iiallon drum of Water left on site <br /> SWRCB December 2001 <br />