Laserfiche WebLink
INDIVIDUA NK/LINE/LEAK DETECTOR T REPORT <br />T <br />TEST DATE: 08/05/98 WORK ORDER NUMBER: 2205434 <br />CLIENT: ULTRAMAR INC SITE: ULTRAMAR 641 <br />Tank ID: 92 <br />Product: SUPER <br />Capacity in gallons: 10,118 <br />Diameter in inches: 128.00 <br />Length in inches: 184 <br />Tank age (years): <br />Fuel pure rating: <br />COMMENTS CP installed on: <br />3 Material: Dw STEEL <br />Tank manifolded: No <br />Vent manifolded: YES <br />Vapor recovery manifolded: YES <br />Impact Valves Operational: Y <br />Overfill protection: YES <br />Overspill protection: YES <br />Dipped Water Level: <br />Dipped Product Level: <br />Probe Water Level: <br />Ingress Detected: Water Bubble <br />Test time: <br />VacuTect Test Type: <br />VacuTect Probe Entry Point: <br />Pressure Set Point: <br />Tank water level in inches: <br />Water table depth in inches: <br />Determined by (method): <br />Result: <br />I COMMENTS <br />Bottom to top fill in inches: <br />Bottom to grade fill in inches: <br />Fill pipe length in inches: <br />Fill pipe diameter in inches: <br />Stage I vapor recovery: <br />Stage II vapor recovery: <br />Installed: <br />na tin/ New/passed Failed/rept, <br />L.D. #1 L.D. #1 <br />Make: RED JACKET <br />Model: FX1 <br />Ullage S/N: 0425965781 <br />Open time in sec: 4.00 <br />Holding psi: 12 <br />Resiliancy cc: 140 <br />Test leak rate ml/m: 189.0 <br />Metering psi: 10 <br />Calib. leak in gph: 3.00 <br />Results: PAss <br />COMMENTS <br />New/passed <br />L.D. #2 <br />192.0 <br />199.0 <br />64.0 <br />4.0 <br />DUAL <br />ASSIST <br />ATG <br />L.D. #2 <br />8900 SHOAL CREEK, BUILDING 200, AUSTIN, TEXAS 78757 (512) 451-6334 Draft 08/11/98 07:56 MSHAW <br />