Laserfiche WebLink
TEST DATE: November 16, 1995 WORK ORDER NUMBER: 965022 <br />CLIENT: TOSCO NORTMEST COMPANY SITE: B.P. 1-1191 <br />Tank ID: <br />i <br />Bottom to top fill in inches: <br />143.0 <br />Product: <br />UNLEAMD <br />Bottom to grade fill in inches: <br />151.0 <br />Capacity in gallons: <br />11,681 <br />Fill pipe length in inches: <br />52.0 <br />Diameter in inches: <br />91.00 <br />Fill pipe diameter in inches: <br />4.0 <br />Length in inches: <br />420 <br />Stage I vapor recovery: <br />DUAL <br />Material: <br />FIBERGLASS <br />Stage 11 vapor recovery: <br />ASSIST <br />Tank: <br />No <br />Open time in sec: 3.00 <br />Manifolded Vent: <br />No <br />Holding psi: 13 <br />V/R: <br />Yzs <br />Resiliency cc: 140 <br />Test method: <br />Alert 1000 <br />Test time: <br />New/passed Failed/replaced <br />Psi at tank bottom: <br />1.45 <br />Ullage pressure: <br />detector detector <br />Fluid level in inches: <br />54.00 <br />DATA FOR UTS-4T ONLY. <br />Test method: FTA <br />UFT/OFT: <br />UPT <br />Test 3: start time: <br />Make: RED JACKET <br />Fluid volume in gallons: <br />7,116 <br />vol change cc: <br />Model: X. L. D. <br />Water level in inches: <br />0.00 <br />RESULT: <br />8/N: 41091397- <br />Test time: <br />23:47-02:14 <br />Open time in sec: 3.00 <br />Number of thermisters: <br />Holding psi: 13 <br />Specific gravity: <br />0.745 <br />Resiliency cc: 140 <br />Water table depth in inches: <br />165.00 <br />Test leak rate ing 189.0 <br />Determined by (method): <br />OBSERVATIO <br />s: <br />Metering psi: 10 <br />psi: <br />Leak rate in gph: <br />0.009 <br />Calib. leak in gph: 3.00 <br />RESULT: <br />PASS <br />RESULT: PASS <br />Test method: <br />Alert 1050 <br />Test time: <br />02:54-03-.24 <br />Ullage volume: <br />4,565 <br />Ullage pressure: <br />1.50 <br />RESULT: <br />PASS <br />DATA FOR UTS-4T ONLY. <br />Time of test 1: <br />Temperature: <br />Flow rate (cfh): <br />Time of test 2: <br />Temperature: <br />Flow rate (cfh): <br />Time of test 3: <br />Temperature: <br />Flow rate (cfh): <br />Diameter (in): <br />2.0 <br />Length (ft): <br />120.0 <br />Test psi: <br />5o <br />Bleedback cc: <br />310 <br />Test time (min): <br />30 <br />Test 1: start time: <br />00:01 <br />finish psi: <br />50 <br />vol change cc: <br />10 <br />Test 2: start time: <br />00: ii <br />finish psi: <br />so <br />vol change cc: <br />3 <br />Test 3: start time: <br />00:21 <br />finish psi: <br />5o <br />vol change cc: <br />o <br />Final gph: <br />0.007 <br />RESULT: <br />PASS <br />Test type: AcuRite <br />Pump type: PREssuRE Pump make: RED JAcxRT <br />