Laserfiche WebLink
Lj <br />INDIVIDU TANK/LINE/LEAK DETECT <br />1 I TEST DATE: November 9, 1994 WORK ORDER NUMBER: 963167 <br />CLIENT: TOSCO NOR ST COMPANY SITE: B.P. 1-1191 <br />Tank ID: <br />1 <br />Bottom to top fill in inches: <br />143.0 <br />Product: <br />REG UNLEAD <br />Bottom to grade fill in inches: <br />151.0 <br />Capacity in gallons: <br />11,681 <br />Fill pipe length in inches: <br />52.0 <br />Diameter in inches: <br />91.00 <br />Fill pipe diameter in inches: <br />4.0 <br />Length in inches: <br />420 <br />Stage I vapor recovery: <br />COAX <br />Material: <br />DW FIBERG <br />Stage II vapor recovery: <br />BALANCE <br />Tank: <br />NO <br />50 <br />vol change cc: <br />Manifolded Vent: <br />No <br />0.018 <br />RESULT: <br />V/K: NO <br />ENTS <br />Test method: <br />VPLT <br />Psi at tank bottom: <br />2.21 <br />Fluid level in inches: <br />82.27 <br />UFT/OFT: <br />UFT <br />Fluid volume in gallons: <br />11,109 <br />Water level in inches: <br />0.00 <br />Test time: <br />14:39-19:30 <br />Number of thermisters: <br />5 <br />Specific gravity: <br />0.743 <br />Water table depth in inches: <br />166.00 <br />Determined by (method): <br />MONTR WELL <br />Leak rate in gph: <br />-0.002 <br />RESULT <br />PASS <br />New/passed Failed/replaced <br />detector detector <br />Test method: FTA <br />Make: RED JACKET <br />Model: X.L.D. <br />S/N: 410913976 <br />Open time in sec: 3.00 <br />Holding psi: 10 <br />Resiliency cc: 280 <br />Test leak rate mVmin: 189.0 <br />Metering psi: 10 <br />Calib. leak in gph: 3.00 <br />RESULT. PASS <br />Test method: <br />UTs-4T system <br />Test time: <br />19:45-20:25 <br />Ullage volume: <br />572 <br />Ullage pressure: <br />1.79 <br />RESULT. <br />PASS <br />DATA FOR UTS-4T ONLY: <br />Time of test 1: <br />Temperature: <br />Flow rate (cfh): <br />Time of test 2: <br />Temperature: <br />Flow rate (cfh): <br />Time of test 3: <br />Temperature: <br />Flow rate (cfh): <br />19:55-20:05 <br />74.80 <br />0.200-0.200 <br />20:05-20:15 <br />74.70 <br />0.200-0.200 <br />20:15-20:25 <br />74.70 <br />0.200-0.150 <br />3MM , <br />WALL <br />Material: STEEL <br />Diameter (in): <br />2.0 <br />Length (ft): <br />75.0 <br />Test psi: <br />5o <br />Bleedback cc: <br />45 <br />Test time (min): <br />30 <br />Test 1: start time: <br />09:15 <br />finish psi: <br />47 <br />vol change cc: <br />25 <br />Test 2: start time: <br />09:25 <br />finish psi: <br />46 <br />vol change cc: <br />10 <br />Test 3: start time: <br />19:35 <br />finish psi: <br />50 <br />vol change cc: <br />0 <br />Final gph: <br />0.018 <br />RESULT: <br />PASS <br />Test type: PTR -88 <br />Pump type: PREssURE Pump make: <br />SUITE <br />7 <br />RED JACKET <br />