Laserfiche WebLink
TANKNOLOGY - UNDERGROUND LEAK DETECTION SYSTEM - (V3.12) Page 22 <br />B P ST # 11191 HO09009-lVE9002025-07904-03 - Sop 22' 1990, 14:04 <br />T& x2v Q k -J --- IF Q il: IF IF E--- E3 IF c3' LJ M M A��� <br />TEST DATE <br />START TIME <br />CLIENT <br />LOCATION NAME <br />LOCATION CODE <br />TANK CONFIGURATION <br />TANK CONTENTS <br />TANK NUMBER <br />TANK DIAMETER <br />TANK CAPACITY <br />TANK MANUFACTURER <br />TANK MATERIAL <br />TANK REGISTRATION # <br />TANK DATE INSTALLED <br />: Sep 22, 1990 <br />: 14:04:27 <br />:BP <br />: B P ST # 11191 <br />: <br />: Tandem <br />: DIESEL/SUPER UNLEAD <br />� 03 <br />: 92 <br />: 6000 <br />: <br />: Fibreglass <br />: <br />INITIAL DIPPED FUEL LEVEL : 59.00 <br />INITIAL DIPPED WATER LEVEL : 0.00 <br />POST PUMPING WATER LEVEL : 0.00 <br />04 <br />92 in <br />10000 8 <br />Fibreglass <br />60.00 in <br />0.00 in <br />0.00 in <br />IF Xv 1*411:0 IF Ew E3 IF F? EO E3KJK_-F <br />TEST INITIAL WATER LEVEL : 0.00 0.00 in <br />TEST FINAL WATER LEVEL : 0.00 0.00 in <br />WATER INGRESS : 0.00 0.00 in <br />BUBBLE SIGNATURES : No No <br />VACU-TECT TEST RESULT `# <br />COMMENTS: TESTED TANKS 3 (DIESEL) AND 4 (SUPER UNLEAD). <br />CONCLUSION: TANKS 3 AND 4 TESTED TIGHT. <br />TEST RATE <br />LINE PRESSURE <br />#1 Passed 50 PSI 0.00 GPH <br />#2 <br />#3 <br />#4 <br />#5 <br />#6 <br />COMMENTS: TESTED LINES 3-A AND 4-A. <br />CONCLUSION: LINES 3-A AND 4-A TESTED TIGHT. <br />TEST RATE <br />Passed 50 PSI 0.00 GPH <br />This test was conducted in accordance with U.S. EPA Rule 40 CFR Parts 280 and 281. <br />