Laserfiche WebLink
Triangle Environmental, Inc. <br /> SYSTEMS TANK, LINE AND LEAK DETECTOR TEST REPORT <br /> Facility: Facility # 2705447 <br /> Tank #. 2 Test Date. 6/27/03 <br /> Product: Unleaded Premium Work#: 20001144 <br /> Test Method: System 4000 Test Method: R.J.FTA <br /> Capacity: 10563 Manufacturer: Vaporless <br /> Diameter(in): L/D Model: LD2000 <br /> Product Level(in): L/D Serial#: <br /> Liquid Volume(Gals): Line Drain Back(ml): 125 <br /> Liquid Percent(%): L/D Trip Time(sec): 2 <br /> Specific Gravity: Holding Pressure(psi): 30 <br /> Coef.of Expansion: Metering Pressure(psi): 21 <br /> Water On Tank(in): L/D Test Rate(gph): 2.9 <br /> Water In Tank(in): L/D Result: PASS <br /> Product Temp. (F): New leak detector? No <br /> Head Pressure(psi): <br /> Test Start Time: MEMENNEMEM <br /> Test End Time: Test Method: TEI LT-3 <br /> Test Rate(gph): Pump Brand: <br /> Test Result: N/A System Type: Pressure <br /> Line Pressure(psi): 52 <br /> INN <br /> Line Start Time: 3:45:00 PM <br /> Test Method: ULLAGE Line End Time: 4:00:00 PM <br /> UllageVolume(gals.): Line Start Level: 210 <br /> Ullage Test Time: Line End Level: 205 <br /> Ullage Vacuum(psi): Line Test Rate(gph): -0.006 <br /> Ullage Result: N/A Line Test Result: PASS <br /> 4 <br />