UNDER DISPENSER CONTAINMENT (UDC) TESTING <br />Test Method By: C Manufacturer • Industry Standard o Professional Engr o Other (see below) <br />Test Method Uses: C' Pressure 0 Vacuum • Hydrostatic o Other (see below) <br />Measuring Equipment Used: iNCON TS4TS (Electronic Sump Test System) <br />rl~--rintinn nicn # 014n <br />UDC manufacturer <br />Brow <br />UDC material <br />FRP <br />UDC depth (Inches) <br />5.4404 <br />Height from UDC bottom to highest <br />ping penetration <br />_ <br />Height from UDC bottom to lowest <br />electrical penetration <br />8 <br />Condition of UDC prior to testing <br />Dry <br />Portion of UDC tested <br />T of shut -down presets <br />Entire <br />FWUSensor <br />Was sensor removed fortes"? <br />Was sensor property replaced alter 7 <br />Yes <br />Yes <br />Depth of water level from UDC bottom (in.) <br />Wait time for water level to stabilize (hrmin) <br />13 <br />0:05 <br />Test start time <br />2:50 PM <br />Initial Probe Reading <br />5.4404 <br />Test end time <br />3:14 PM <br />Final Probe Readkg <br />5,4407 -- <br />Test duration (hr:min) <br />0:15 <br />Change in water level (* 0.0000 irac m) <br />— <br />0.0003—^ <br />Pass/Fad threshold (*0.0020 4khes I } Hr.) <br />0.0020 <br />TEST RESULT <br />PASS <br />Comments: <br />