Laserfiche WebLink
7�"'Mff- W <br /> PRESSURIZED PIPING LEAK DETECTION CERTIFICATION SHEET <br /> Date: 711612012 Work Order# 12071601-7 <br /> Location: CRLLC#5447 Contact: ALLEN FAASS <br /> 1469 E.HAMMER LANE <br /> STOCKTON, CA 95209 Telephone: (925)884-0800 <br /> SUMP# <br /> PRODUCT 91 89 87 DIESEL <br /> LD TYPE Mechanical, (W)PLLD, (P)LLD I M M M M <br /> LD MANUFACTURER VMI VMI VMI VMI <br /> LD MODEL LD 2000 LD 2000 LD 2000 LD 2000 <br /> LD SERIAL NUMBER 1011249 09041087 11071266 07081287 <br /> SUMP CONDITION DRY DRY DRY DRY <br /> RESILIENCY 150 ML 155 ML 150 ML 150 ML <br /> OPERATING PRESSURE 26 PSI 26 PSI 26 PSI 28 PSI <br /> OPENING TIME 3 SEC 4 SEC 3 SEC 6 SEC <br /> METERING PRESSURE 10 PSI 10 PSI 10 PSI 10 PSI <br /> FUNCTIONAL ELEMENT HOLDING PRESSURE 18 PSI 18 PSI 18 PSI 18 PSI <br /> LEAK RATE LD DETECTED 3 GPH 3 GPH 3 GPH 3 GPH <br /> DOES LD DETECT 3 GPH LEAK RATE? YES YES YES YES <br /> DOES VEEDER-ROOT CONSOLE ALARM? N/A N/A N/A N/A <br /> LD PASS OR FAIL? PASS PASS PASS PASS <br /> Comments: <br /> Technician: RICHARD THOMAS Contractor Lic. # 803705 <br /> Signature: <br /> N L <br /> TANK"TEK ENVIRONMENTAL CORPORATION <br /> 607 Elmira Road, PMB 336,Vacaville,CA 95687 — Ph.(707)446-6151 - Fax (707)446-6192 <br /> 31828 Cercle Chambertin,Temecula, CA 92591 — Ph. (951)699-8058 - Fax(951)699-8059 - E-mail:bballreich@verizon.net <br />